Plan Review Notes
Plan Review Notes For Permit 21110869
Permit Number 21110869
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-11-23 14:26:57SPECIFY DISTANCES FROM HVAC REGISTERS PER TABLE 8.3.2.5
 NFPA 13
 SPECIFY MAXIMUM DISTANCE BETWEEN HANGERS PER TABLE
 9.2.2.1 NFPA 13
 SPECIFY HOW HYDROSTATIC TESTING WILL BE CONDUCTED PER
 SECTION 25.2.1 NFPA 13
  