2022-04-01 15:55:52 | ELECTRIC REVIEW FAILED |
| 1) METER IS INCORRECTLY DESCRIBE AS A 120/208 VOLT |
| METER CAN. PLEASE DETAIL IT CORRECTLY. FBC 107.2 |
| 2) RISER DIAGRAM DETAILS (2) SETS OF 500MCM RHU AS |
| FEEDERS TO THE EXISTING 1000-AMP MDP. THESE CONDUCTORS |
| ARE INADEQUATELY SIZED AS PER NEC 240.4(C). OVERCURRENT |
| DEVICE OVER 800-AMPERES, THE AMPACITY OF CONDUCTORS IT |
| PROTECTS SHALL BE EQUAL TO OR GREATER THE RATING OF THE |
| OVERCURRENT DEVICE. PLEASE CORRECT WITH APPROPRIATELY |
| SIZED CONDUCTORS. |
| 2) THE RISER DIAGRAM DOES NOT DETAIL GROUND FAULT |
| PROTECTION AS REQUIRED PER NEC 215.10 FOR DISCONNECTS |
| OF 480 VOLT,1000AMP SYSTEMS. PLEASE DETAIL THAT THIS |
| GROUND FAULT PROTECTION EXISTS OR WILL BE INSTALLED. |
| 3) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION |
| AND ENSURE EQUIPMENT RATING IS SUFFICIENT AS PER NEC |
| 110.9. PLEASE INCLUDE A NOTE TO ENSURE LABLEING TO IS |
| TO BE APPLIED ON EQUIPMENT AS PER NEC 110.24 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |