Plan Review Notes
Plan Review Notes For Permit 21110846
Permit Number 21110846
Review Stop E
Sequence Number 1
Notes
Date Text
2021-12-13 10:22:52 PLEASE CORRECT
 1) SERVICE POINT DETAILS INDICATE #2 RHW CU FEEDER
 CONDUCTORS FROM SERVICE POINT ?A? TO SERVICE POINT ?B?
 WITH 125-AMP OVERCURRENT PROTECTION. NEC TABLE 310.15
 (B)(16) STATES AMPACITY OF THIS CONDUCTOR AT 115-AMPS
 2) PLAN ALSO STATES THERE ARE NO EXISTING LOADS AT
 EXISTING SERVICE POINT ?A?. IS THERE MORE THAN ONE
 SERVICE AT THE EXISTING STORAGE BUILDING? PLEASE DETAIL
 LOCATIONS OF EXISTING SERVICES AT THE EXISTING
 BUILDINGS AND WHAT ELECTRICAL LOADS THESE SERVICES
 SUPPLY. F.B.C.107.3.5.1.2
 3) NEC210.20 (A) OVERCURRENT PROTECTION OF 20-AMPS IS
 NOT ADEQUATE TO SUPPLY TENNIS COURT LIGHT CIRCUITS WITH
 A CONTINUOUS LOAD OF 17.3-AMPS
  