Plan Review Notes For Permit 21110846 |
Permit Number |
21110846 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-13 10:22:52 | PLEASE CORRECT | | 1) SERVICE POINT DETAILS INDICATE #2 RHW CU FEEDER | | CONDUCTORS FROM SERVICE POINT ?A? TO SERVICE POINT ?B? | | WITH 125-AMP OVERCURRENT PROTECTION. NEC TABLE 310.15 | | (B)(16) STATES AMPACITY OF THIS CONDUCTOR AT 115-AMPS | | 2) PLAN ALSO STATES THERE ARE NO EXISTING LOADS AT | | EXISTING SERVICE POINT ?A?. IS THERE MORE THAN ONE | | SERVICE AT THE EXISTING STORAGE BUILDING? PLEASE DETAIL | | LOCATIONS OF EXISTING SERVICES AT THE EXISTING | | BUILDINGS AND WHAT ELECTRICAL LOADS THESE SERVICES | | SUPPLY. F.B.C.107.3.5.1.2 | | 3) NEC210.20 (A) OVERCURRENT PROTECTION OF 20-AMPS IS | | NOT ADEQUATE TO SUPPLY TENNIS COURT LIGHT CIRCUITS WITH | | A CONTINUOUS LOAD OF 17.3-AMPS | | |
|