Plan Review Notes For Permit 21110845 |
Permit Number |
21110845 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-12-29 06:06:10 | IT APPEARS THAT THE 1ST LEVEL APARTMENT AHU IS LOCATED | | IN A CLOSET AND I DO NOT SEE A RETURN AIR GRILL DUCTED | | TO OUTSIDE OF THE CLOSET. PLEASE SHOW HOW THE RETURN | | AIR PATH IS NOT USING THE CLOSET TO GET BACK TO THE | | AHU. FBC RES M1602.2-4 | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|