2021-12-01 17:30:16 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21110737 |
| 12/1/21 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1. PLEASE CLEARLY INDICATE WHAT TYPE OF FLUIDS WILL BE |
| DISCHARGED INTO THE 2 FLOOR DRAINS IN THE GARAGE FLOOR. |
| IT WOULD APEAR AS THOUGH THIS GARAGE WILL BE USED TO |
| WASH OFF/ DETAIL THE VEHICLES. NO OIL, SAND OR OTHER |
| SUBSTANCES SHALL BE DISHARGED INTO THE CITYS SANITARY |
| SEWER SYSTEM. AN OIL AND SAND TRAP WOULD BE REQUIRED TO |
| SEPERATE THIS. PLEASE CLEARIFY .WPB CODE OF ORDINANCES |
| SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF |
| DISCHARGE. (3)POLLUTANTS WHICH CREATE A FIRE OR |
| EXPLOSION HAZARD IN THE WWF. PROHIBITED MATERIALS |
| INCLUDE, BUT ARE NOT LIMITED TO, PETROLEUM OIL AND |
| NON-BIODEGRADABLE CUTTING OIL, GASOLINE, KEROSENE, FUEL |
| OIL, MOTOR OIL, NAPHTHA, BENZENE, TOLUENE, XYLENE, |
| ETHERS, ALCOHOLS, KETONES, ALDEHYDES, PEROXIDES, |
| CHLORATES, PERCHLORATES, BROMATES, CARBIDES, HYDRIDES, |
| AND SULFIDES OR ANY OTHER SUBSTANCE WHICH THE CITY, THE |
| STATE, OR ANY FEDERAL AGENCY HAS DETERMINED IS A FIRE |
| HAZARD OR A HAZARD TO THE WWF. |
| |
| 2. FLOOR DRAINS REQUIRE TRAP PRIMMERS TO BE INSTALLED |
| PER FBC P 2020 -901.2 |
| |
| 3. MINIMUM OF 1 SANITARY VENT SHALL BE RAN THROUGH THE |
| ROOF PER FBC P 904.1 |
| |
| 4. PRESSURE VACUUM BREAKERS ARE REQUIRED FOR HOSE BIBBS |
| AS PER FBC P608.16 |
| |
| 5. SEPERATE PERMIT REQUIRED FOR THE RELOCATION OF THE |
| IRRIGATION AND THE WATER PURIFIER. WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 6. A SANITARY 2-WAY CLEAN OUT SHALL BE INSTALLED IN THE |
| SEWER LINE WHERE THE SANITARY SEWER METS THE BUILDING |
| MAIN DRAIN LINE ON THE EXTERIOR OF THE GARAGE.AS PER |
| FBC P708.1.3 |
| |
| 7. HOW WILL HOT WATER BE SUPPLIED TO THE NEW SINK IN |
| THE GARAGE? AS PER FBC P607.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |