2021-11-18 13:24:05THE LOAD CALCULATIONS IS CALLING FOR 600 CFM'S OF
 SUPPLY FOR THE MECHANICAL SYSTEM BUT THE REGISTERS ON
 THE MECHANICAL DRAWING ADD UP TO 690 CFM'S. PLEASE BE
 CONSISTENT ON BOTH SUBMITTALS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  