Plan Review Notes For Permit 21110664 |
Permit Number |
21110664 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-01 14:09:01 | PROVISO NOTE 1: SPRINKLER TO BE INSTALLED AT THE TOP OF | | ELEVATOR HOISTWAY NFPA 13 8.15.5.5 | | PROVISO NOTE 2: PROVIDE FDC SIGNAGE TO COMPLY WITH NFPA | | 13 8.17.2.4.7 | | |
|