2021-12-30 13:30:011ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110622
 12/30/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3.3- DETAILS 5 & 8: SHOW THE TOILET SEAT
 MEASUREMENTS FROM THE FINISHED FLOORS TO THE TOPS OF
 THE SEATS- SEC. 604.4 FBC ACC.
  
 2) A3.3- DETAILS 4 & 7: SHOW THE REAR WATER CLOSET GRAB
 BARS WILL BE 36-INCHES MINIMUM LENGTH AND SHALL EXTEND
 FROM THE CENTERLINE OF THE WATER CLOSETS 12 INCHES
 MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE OTHER
 SIDE- SEC. 604.5.2 FBC ACC.
  
 3) A3.3 DETAILS D, 10, 11: SHOW THE SHOWER GRAB BARS
 WILL BE INSTALLED 6 INCHES MAXIMUM FROM THE ADJACENT
 WALLS- SEC. 608.3.2 FBC ACC.
  
 4) A3.3 DETAIL 10: SHOW THE INSTALLATION HEIGHT OF THE
 SHOWER CONTROLS, FAUCETS, AND SHOWER SPRAY- SEC.
 608.5.2 FBC ACC.
  
 5) A3.3: PROVIDE SHOWER PAN DRAIN, LINER, AND WALL
 FINISH DETAILS- SECS. 417.3, 417.4.1, & 417.5.2 FBC P.
  
 6) P1.1 & P1.2: THE WASHING MACHINE FIXTURE DRAIN SHALL
 CONNECT TO A 3-INCH STACK OR BRANCH DRAIN- SEC. 406.2
 FBC P.
  
 7) P2.1: SHOW THE LOCATIONS OF THE WASHING MACHINE
 SHUTOFF VALVES OR PROVIDE A NOTE TO INDICATE THEY WILL
 IN AN ACCESSIBLE LOCATION- SEC. 608.3 FBC P.
  
 8) P2.2: PROVIDE SYMBOLS TO SHOW THE LOCATIONS OF
 SHUTOFF VALVES AND WATER HAMMER ARRESTORS- SECS. 606.1,
 606.2 & 604.9 FBC P.
  
 9) P2.1 & P2.2: INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 416.5 FBC P.
  
 10) P3.1: PROVIDE THE MAKE AND MODEL OF SHOWER VALVE IN
 THE SCHEDULE AND SHOW COMPLIANCE WITH SEC. 412.3 FBC P.
  
 11) P3.1: INCLUDE WATER CLOSET FLUSH VALVES IN THE
 FIXTURE CONNECTION SCHEDULE- TABLE 604.5 FBC P.
  
 12) P3.2: PROVIDE AN ENLARGED WATER PIPING DETAIL FOR
 THE NEW WATER HEATERS SHOWING WATER PIPING SUPPLY AND
 RETURN CONNECTIONS, LOCATIONS OF CONTROLS, VALVES,
 EXPANSION TANK (IF REQUIRED), PRESSURE RELIEF PIPING,
 AND CONDENSATE PIPING- SECS. 502.1, 607.2.1- 607.3 FBC
 P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  