Plan Review Notes For Permit 21110622 |
Permit Number |
21110622 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-20 13:39:20 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21110622 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SHOW WHERE THE OXYGEN WILL BE STORED AND THE | | AMOUNTS FOR THE HYPERBARIC CHAMBER. FBC 107.2.1 | | | | 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | USE OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | 3) PLEASE MAKE SURE THE BATH EXHAUST FANS WILL MEET THE | | MINIMUM CFM REQUIREMENTS OF FBC M TABLE 403.3.1.1 FOOT | | NOTE E 50 CFM IF CONTINUOUSLY OPERATED OR 70 CFM IF | | INTERMITTENTLY OPERATED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|