Plan Review Notes
Plan Review Notes For Permit 21110622
Permit Number 21110622
Review Stop M
Sequence Number 1
Notes
Date Text
2021-12-20 13:39:201ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110622
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW WHERE THE OXYGEN WILL BE STORED AND THE
 AMOUNTS FOR THE HYPERBARIC CHAMBER. FBC 107.2.1
  
 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 3) PLEASE MAKE SURE THE BATH EXHAUST FANS WILL MEET THE
 MINIMUM CFM REQUIREMENTS OF FBC M TABLE 403.3.1.1 FOOT
 NOTE E 50 CFM IF CONTINUOUSLY OPERATED OR 70 CFM IF
 INTERMITTENTLY OPERATED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  