Plan Review Notes
Plan Review Notes For Permit 21110547
Permit Number 21110547
Review Stop P
Sequence Number 2
Notes
Date Text
2022-02-07 14:48:572ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21110547
 2/7/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET EP-1: THE NEW UTILITY SINK AND KITCHEN SINK
 REQUIRE HOT WATER AT MINIMUM 110 DEGREES F, HOWEVER THE
 SPECIFIED CHRONOMITE INSTA-HOT WATER HEATER HAS AN
 INTEGRAL MIXING VALVE WHICH WILL DELIVER TEMPERED WATER
 BETWEEN 85 AND 110 DEGREES. THIS UNIT CANNOT BE USED-
 SECS. 202 AND 607.1 FBC P.
  
 2) EP-1: SHOW THE LOCATIONS OF THE REQUIRED FULL OPEN
 SHUT OFF VALVES AND CHECK VALVES FOR THE SUMP PUMP
 DISCHARGE LINES AND VERIFY THEY WILL BE ACCESSIBLE-
 SEC. 712.2 FBC P. A) PLEASE SHOW THE DISCHARGE PIPING
 SHALL CONNECT TO THE TOP OF THE 3-INCH SANITARY LINE
 USING A WYE FITTING- SEC. 712.3.5 FBC P.
  
 3) EP-1: PLEASE CORRECT THE NOTE SPECIFYING 5/8-INCH
 THICK INSULATION FOR HOT WATER PIPING- 1-INCH THICK IS
 REQUIRED PER TABLE C403.2.10 FBC EC.
  
 4) A-4 & EP-1: CONCERNING THE NEW MOP SINK PLEASE SEE
 SEC. 310.3 FBC P AND SEC.1210.2.2 FBC B. WALLS AND
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 5) A-4 & EP-1: THE DOOR SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR THE LAVATORY UNLESS MEETING
 EXCEPTION 2 UNDER SEC. 603.2.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  