Plan Review Notes
Plan Review Notes For Permit 21110547
Permit Number 21110547
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-03 17:03:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21110547
 12/3/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS CS, A1, EP-1: REFER TO SECTION 810.1 FBC EX-
 IT APPEARS THE OCCUPANT LOAD OF THE TENANT SPACE HAS
 INCREASED BY MORE THAN 20 % WHICH REQUIRES PLUMBING
 FIXTURES TO BE PROVIDED IN QUANTITIES AS SPECIFIED IN
 THE FBC P. THE PLUMBING FIXTURE CALCULATIONS ON SHEET
 CS INDICATE WATER CLOSETS AND LAVATORIES FOR BOTH MALE
 AND FEMALE HOWEVER THE PLANS INDICATE A MALE TOILET
 ROOM ONLY. REFER TO TABLE 403.1 AND SECTION 403.2 FBC P
 AND PROVIDE A TOILET ROOM FOR FEMALE USE. PLEASE NOTE
 THAT SEPARATE FACILITIES ARE REQUIRED- REVISE THE PLANS
 ACCORDINGLY.
  
 2) CS, A1, EP-1: REFER TO TABLE 403.1 FBC P: DRINKING
 FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR S
 OCCUPANCIES. PLEASE REVISE THE PLANS TO SHOW THE
 LOCATIONS OF THE FIXTURES AND PLUMBING PIPING DETAILS-
 SECTION 107.2.1 WPB.
  
 3) SHEET A1: SHOW THE MINIMUM LENGTHS OF THE WATER
 CLOSET GRAB BARS AS THEY ARE INDICATED IN SECTION 604.5
 & FIGURES 604.5.1 & 604.5.2 FBC ACC.
  
 4) A1: REFER TO SECTION 606.2 AND FIGURES 306.2 & 306.3
 FBC ACC AND SHOW THE CORRECT KNEE AND TOE CLEARANCES
 FOR THE LAVATORY.
  
 5) A1: REFER TO SECTION 606.2 AND FIGURES 306.2 & 306.3
 FBC ACC PLEASE PROVIDE A DETAIL DEPICTING THE KNEE AND
 TOE CLEARANCES AT THE BREAKROOM SINK- SECTION 606.2 AND
 FIGURES 306.2 & 306.3 FBC ACC.
  
 6) EP-1: THE RISER DRAWINGS DO NOT INDICATE PIPING FOR
 THE TOILET ROOM FIXTURES- SECTION 107.2.1 WPB.
  
 7) EP-1: INDICATE THE SOURCE OF THE HOT WATER FOR THE
 FIXTURES- SECTION 607.1 FBC P.
  
 8) EP-1: INDICATE HOW TEMPERED WATER WILL BE DELIVERED
 FROM THE LAVATORIES- 419.5 FBC P.
  
 9) EP-1: REFER TO SECTION & TABLE C404.5.1 FBC EC FOR
 MAXIMUM ALLOWABLE LENGTHS OF HW PIPING FROM THE HW
 SOURCE TO THE FIXTURE SUPPLY PIPE AT THE LAVATORIES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  