2021-12-15 10:25:41** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) GENERATOR SETBACK FROM THE PROPERTY LINES NOT
 PROVIDED. PLEASE PROVIDE THE SETBACK
 DISTANCE/DIMENSIONS IN THE PLAN. THE QUALITY OF THE
 SCANNED SURVEY IS ALSO DIFFICULT TO READ. PLEASE NOTE
 THAT THE GENERATOR MAY NOT PROJECT MORE THAN 4 FT. INTO
 THE REQUIRED SETBACK (FRONT =25 FT.; INTERIOR SIDE = 15
 FT.)
  
 2.) A SCREEN (I.E. LANDSCAPING, FENCE/WALL, ETC.) MAY
 BE NECESSARY TO SCREEN THE LOCATION OF THE PROPOSED
 GENERATOR FROM THE RIGHT-OF-WAY, ADJACENT PROPERTY.
  
 NOTES:
  
 ANY REVISIONS/RESUBMITTAL MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: RPD (IRONHORSE ESTATE)
  
 REFERENCE: ORDINANCE NOS. 2189-88 AND 2729-94
  