Permit Number |
21110534 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-15 10:25:41 | ** FAILED ** | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | APPLICABLE: | | | | 1.) GENERATOR SETBACK FROM THE PROPERTY LINES NOT | | PROVIDED. PLEASE PROVIDE THE SETBACK | | DISTANCE/DIMENSIONS IN THE PLAN. THE QUALITY OF THE | | SCANNED SURVEY IS ALSO DIFFICULT TO READ. PLEASE NOTE | | THAT THE GENERATOR MAY NOT PROJECT MORE THAN 4 FT. INTO | | THE REQUIRED SETBACK (FRONT =25 FT.; INTERIOR SIDE = 15 | | FT.) | | | | 2.) A SCREEN (I.E. LANDSCAPING, FENCE/WALL, ETC.) MAY | | BE NECESSARY TO SCREEN THE LOCATION OF THE PROPOSED | | GENERATOR FROM THE RIGHT-OF-WAY, ADJACENT PROPERTY. | | | | NOTES: | | | | ANY REVISIONS/RESUBMITTAL MAY RESULT IN ADDITIONAL | | COMMENTS. | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. | | | | * ZONE: RPD (IRONHORSE ESTATE) | | | | REFERENCE: ORDINANCE NOS. 2189-88 AND 2729-94 | | |
|