Plan Review Notes
Plan Review Notes For Permit 21110473
Permit Number 21110473
Review Stop B
Sequence Number 2
Notes
Date Text
2021-12-08 14:58:43WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21110473
 ADD: 2450 PRESIDENTIAL WAY # 1908
 PCN:74-43-43-18-10-000-1908
 CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC
 TEL: 561-588-7353
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. DEC. 08TH/ 2021
 ACTION: DENIED
  
 1) 2ND REQUEST. THE WRIGHT?S FLOOR PLAN & OPENING
 SCHEDULE(WIND LOAD CHART) NEEDS TO SHOW WHO THE AUTHOR
 IS OF THE PLAN. CERTIFICATION BY CONTRACTOR. 107.3.4.3.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2A) 2ND REQUEST. DRAWING 1 WRIGHT?S FLOOR PLAN DOES NOT
 SHOW THE FLOOR PLAN IN THE OVER ALL CURVATURE OF THE
 BUILDING, NOR THE UNITS THAT ARE PROJECTED FURTHER OUT
 THAN OTHER PORTIONS OF THE WALL LINE CREATING A
 FLUTTERING OR GALLOPING AFFECT. THE ENGINEERING SHEET
 STATES THE MINIMUM BUILDING WIDTH OF 50 FEET. ASSUMED
 VALUE FOR END ZONE WIDTH FROM A CORNER IS 5 FEET.
 PLEASE PROVIDE THE DISTANCE AWAY FROM THE CORNER FOR
 WINDOW IDENTIFIED AS NUMBER 9.
  
 2B) ENGINEERING EXPRESS SHEET SHOWS FOR COMPLEX
 BUILDINGS USE CORNER ZONES IF AT ALL IN QUESTION. THIS
 WILL GREATLY AFFECT THE PRESSURES ON THESE OPENINGS AND
 SUBMITTED SCHEDULE.
 BUILDING END ZONES (5). THE FLOOR PLAN LAYOUT INDICATES
 THE WORK TO BE PERFORMED UNDER THIS PERMIT IS A CORNER
 UNIT OF A HIGHRISE BUILDING. THE WIND LOAD CHART UNDER
 NOTES STATES WHAT IS CONSIDERED AN END ZONE 10% OF THE
 LEAST HORIZONTAL DISTANCE OF THE BUILDING OR 40% OF THE
 MRH, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL
 DISTANCE OR 3 FT. THE CONTRACTOR HAS NOT IDENTIFIED
 WHAT THE LEAST HORIZONTAL DISTANCE IS FOR THE BUILDING
 NOR THE LOCATION OF THE UNIT IN RELATIONSHIP TO THE
 BUILDING AND THE INTERCOASTAL WATERWAY. EXAMPLE ONLY.
 IF THE BUILDING HEIGHT IS APPROXIMATELY 180 FT. (MRH.)
 X 0.40= 72 FEET. THIS WOULD PUT ALL OPENINGS IN WIND
 ZONE 5 OR 10% OF THE LEAST HORIZONTAL DISTANCE OF THE
 BUILDING, ALSO UNKNOWN.
  
 2B) 2ND REQUEST. THE ENGINEERING SHEET STATES A
 BUILDING HEIGHT OF 240 FT., WRIGHTS WIND LOAD CHART
 STATES 240 FEET BUT THE FLOOR PLAN STATES THE BUILDING
 HEIGHT OF 200 FEET. DISCREPANCY IN PLANS. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3A) THE FLORIDA APPROVAL FL 27914-R2 IDENTIFY GLAZING/
 MULLIONS. PLEASE IDENTIFY IN THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE,
 LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 3B) THE FLORIDA APPROVAL FL 27914-R2 DOES NOT GIVE THE
 POSITIVE PRESSURES FOR THE SILL. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  