Date |
Text |
2021-12-08 14:58:43 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21110473 |
| ADD: 2450 PRESIDENTIAL WAY # 1908 |
| PCN:74-43-43-18-10-000-1908 |
| CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC |
| TEL: 561-588-7353 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. DEC. 08TH/ 2021 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. THE WRIGHT?S FLOOR PLAN & OPENING |
| SCHEDULE(WIND LOAD CHART) NEEDS TO SHOW WHO THE AUTHOR |
| IS OF THE PLAN. CERTIFICATION BY CONTRACTOR. 107.3.4.3. |
| THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| AND PLANS DRAWN. |
| |
| 2A) 2ND REQUEST. DRAWING 1 WRIGHT?S FLOOR PLAN DOES NOT |
| SHOW THE FLOOR PLAN IN THE OVER ALL CURVATURE OF THE |
| BUILDING, NOR THE UNITS THAT ARE PROJECTED FURTHER OUT |
| THAN OTHER PORTIONS OF THE WALL LINE CREATING A |
| FLUTTERING OR GALLOPING AFFECT. THE ENGINEERING SHEET |
| STATES THE MINIMUM BUILDING WIDTH OF 50 FEET. ASSUMED |
| VALUE FOR END ZONE WIDTH FROM A CORNER IS 5 FEET. |
| PLEASE PROVIDE THE DISTANCE AWAY FROM THE CORNER FOR |
| WINDOW IDENTIFIED AS NUMBER 9. |
| |
| 2B) ENGINEERING EXPRESS SHEET SHOWS FOR COMPLEX |
| BUILDINGS USE CORNER ZONES IF AT ALL IN QUESTION. THIS |
| WILL GREATLY AFFECT THE PRESSURES ON THESE OPENINGS AND |
| SUBMITTED SCHEDULE. |
| BUILDING END ZONES (5). THE FLOOR PLAN LAYOUT INDICATES |
| THE WORK TO BE PERFORMED UNDER THIS PERMIT IS A CORNER |
| UNIT OF A HIGHRISE BUILDING. THE WIND LOAD CHART UNDER |
| NOTES STATES WHAT IS CONSIDERED AN END ZONE 10% OF THE |
| LEAST HORIZONTAL DISTANCE OF THE BUILDING OR 40% OF THE |
| MRH, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL |
| DISTANCE OR 3 FT. THE CONTRACTOR HAS NOT IDENTIFIED |
| WHAT THE LEAST HORIZONTAL DISTANCE IS FOR THE BUILDING |
| NOR THE LOCATION OF THE UNIT IN RELATIONSHIP TO THE |
| BUILDING AND THE INTERCOASTAL WATERWAY. EXAMPLE ONLY. |
| IF THE BUILDING HEIGHT IS APPROXIMATELY 180 FT. (MRH.) |
| X 0.40= 72 FEET. THIS WOULD PUT ALL OPENINGS IN WIND |
| ZONE 5 OR 10% OF THE LEAST HORIZONTAL DISTANCE OF THE |
| BUILDING, ALSO UNKNOWN. |
| |
| 2B) 2ND REQUEST. THE ENGINEERING SHEET STATES A |
| BUILDING HEIGHT OF 240 FT., WRIGHTS WIND LOAD CHART |
| STATES 240 FEET BUT THE FLOOR PLAN STATES THE BUILDING |
| HEIGHT OF 200 FEET. DISCREPANCY IN PLANS. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3A) THE FLORIDA APPROVAL FL 27914-R2 IDENTIFY GLAZING/ |
| MULLIONS. PLEASE IDENTIFY IN THE PRODUCT APPROVAL |
| BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE, |
| LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF |
| REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH |
| OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. |
| WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH |
| APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND |
| SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND |
| SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING |
| USED IN THE TESTS. |
| |
| 3B) THE FLORIDA APPROVAL FL 27914-R2 DOES NOT GIVE THE |
| POSITIVE PRESSURES FOR THE SILL. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |