Plan Review Notes
Plan Review Notes For Permit 21110465
Permit Number 21110465
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-29 08:36:5611/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A DRAWING WAS SUBMITTED FOR PLUMBING WORK BUT THE
 CITY OF WEST PALM BEACH HAS NO RECORD OF A DEMO OR
 BUILDING WORK FOR THAT STRUCTURE. WOULD YOU PLEASE
 PROVIDE A LAYOUT OF WHAT IS BEING DEMO OR ADDED, THE
 SOURCE OF HOT WATER? SEPARATE PERMIT REQUIRED PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1. PLEASE REFER TO
 BUILDING COMMENTS.
  
 2. WHERE ARE THE TWO UNITS ON THE SECOND FLOOR
 CONNECTING TO THE BUILDING DRAIN AND WHAT SIZE IS THE
 FIXTURE LOAD PER THE 2020 FBC TABLE 710.1(1) BUILDING
 DRAINS AND SEWER.
  
 3. WOULD YOU PLEASE SHOW THE LOCATION OF WATER HEATERS
 PER THE WPB AMEND TO FBC 107.2.1.
  
 4. IF WATER PIPING IS BEING REPLACED, PLEASE PROVIDE A
 WATER ISOMETRIC PER THE WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 5. A BACKFLOW DEVICE WILL BE REQUIRED ON THE WATER
 SERVICE AT THE METER A SEPARATE PERMIT WILL BE
 REQUIRED. PER WPB UTILITIES DEPARTMENT CROSS CONNECTION
 MANUAL.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  