2021-11-29 08:33:03 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) IT APPEARS THAT YOU INTEND TO REPLACE ALL OF THE |
| PLUMBING IN A TWO STORY (4) UNIT APARTMENT BUILDING |
| THAT WAS CONSTRUCTED IN 1930. THIS WORK WILL REQUIRE |
| THE WALLS, FLOORS AND CEILINGS TO BE OPENED FOR ACCESS |
| TO REPLACE THE EXISTING PLUMBING. THE TENANT SEPARATION |
| WALLS BETWEEN THE UNITS ARE REQUIRED TO HAVE A ONE HOUR |
| FIRE RESISTIVE RATING. A BUILDING CONTRACTOR IS |
| REQUIRED TO OBTAIN A PERMIT TO COMPLETE THIS WORK. FBC |
| AMENDMENTS 105.1 |
| |
| 2) PROVIDE A FULL SCOPE OF WORK. SPECIFY IF NEW |
| FIXTURES, VANITIES AND KITCHEN CABINETS WILL BE |
| INSTALLED. FBC AMENDMENTS 107.2.1 |
| |
| 3) PROVIDE AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR |
| PLAN. FBC AMENDMENTS 107.2 |
| |
| 4) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS PER THE |
| FBC EXISTING BUILDING CHAPTER 6. |
| |
| 5) PROVIDE DETAILS FOR THE ONE HOUR FIRE RESISTANCE |
| RATED TENANT SEPARATION WALLS AND FOR THE PROTECTION OF |
| OPENINGS OR PENETRATIONS IN THESE WALLS. FBC 714 |
| |
| 6) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. PLEASE NOTE |
| THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS |
| MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |