2022-07-18 13:51:02 | PETER E VALENTI |
| BUILDING PLANS EXAMINER II |
| [email protected] |
| 561 805 6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC M = FBC MECHANICAL |
| FBC FG = FBC FUEL GAS |
| |
| BUILDING REVIEW DENIED: |
| |
| 2.) 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES WITHIN THE FIRST 10 FEET. |
| |
| 3. PLAN SHEET A-7 INDICATES R-30 BATT INSULATION AT |
| ROOF. |
| FBC B 107.2.1,PROVIDE, ON PLAN SHEETS THE WALL |
| INSULATION TYPE FOR CMU/MASONRY AND WOOD FRAMING TO |
| MATCH THE SUBMITTED ENERGY CALC. FORM R-405. |
| FBC EC R 103.1.1.2, OWNER/OWNER AGENT MUST SIGN THE |
| COMPLETED FORM R-405. |
| |
| |
| 5.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE |
| R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES |
| R301.2.1.1WIND DESIGN REQUIRED. |
| |
| 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN |
| PRESSURES. |
| TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE?SUBMITTAL FORM. |