2021-11-19 07:11:25 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21110446 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS FOR THE |
| NEWLY CONDITIONED GUEST HOUSE. FBC EC R402.1 |
| |
| 2) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEWLY |
| CONDITIONED GUEST HOUSE. FBC EC R403.7 |
| |
| 3) PLEASE PROVIDE ANCHORAGE DETAILS FOR THE CONDENSING |
| UNIT FOR THE GUEST HOUSE. FBC RES M1307.2 |
| |
| 4) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW |
| ADDITION. FBC EC R402.1 |
| |
| 5) PLEASE PROVIDE THE MECHANICAL SIZING CALCULATIONS |
| FOR THE NEW ADDITION. FBC EC R403.7 |
| |
| 6) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE |
| MECHANICAL SYSTEM AND DUCTWORK FOR THE NEW ADDITION. |
| FBC 107.2.1 |
| |
| 7) PLEASE PROVIDE INFORMATION ON THE KITCHEN HOOD, CFM |
| OF EXHAUST, MAKE UP AIR REQUIRED? FBC RES M1503.1 |
| |
| 8) PLEASE SHOW THE DRYER DUCT AND TERMINATION LOCATION. |
| FBC RES M1502 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |