2022-01-05 17:04:13 | BUILDING PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE DEMENSIONS TO PROPERTY LINES ON SITE PLAN. |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE |
| SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| ACCURATE AND INCLUDED BOUNDARY LINE SURVEY. |
| |
| 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES WITHIN THE FIRST 10 FEET. |
| |
| 3. PROVIDE AN ENERGY SUBMITTAL. |
| CEILING INSULATION ON PLAN PAGE A-1 IS LISTED AS R-19. |
| WHAT TYPE OF INSULATION WILL BE INSTALLED? |
| STATE THE EXT. WALL INSULATION TYPE AND R-VALUE ON |
| PLAN. |
| FBC 107.3.5.1.6 ENERGY CALCULATIONS ? PROVIDE AN ENERGY |
| SUBMITTAL COMPLIANT WITH FBC-E 103; |
| FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| STORIES. |
| FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE |
| ALTERNATIVE. |
| R405.2 EC. |
| |
| 4. REFERENCE PAGE C-1 FOR THE FOLLOWING: |
| BUILDING DATA: NEW A/C AREA IS STATED AS 224 SF. |
| (PATIO/PORCH) |
| WILL THE GARAGE CONVERSION BE CONDITIONED SPACE? |
| PLEASE CLARIFY? |
| |
| 5.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE |
| R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES |
| R301.2.1.1WIND DESIGN REQUIRED. |
| |
| 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN |
| PRESSURES. |
| TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| |
| 7. REFERENCE PLAN PAGE A-8 FOR THE FOLLOWING: |
| ELEVATION VIEWS APPEAR TO BE A MIRROR IMAGE OF THE |
| FLOOR PLAN. PLEASE CLARIFY? |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |
| |
| |
| |