Plan Review Notes
Plan Review Notes For Permit 21110446
Permit Number 21110446
Review Stop B
Sequence Number 1
Notes
Date Text
2022-01-05 17:04:13BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DEMENSIONS TO PROPERTY LINES ON SITE PLAN.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDARY LINE SURVEY.
  
 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 3. PROVIDE AN ENERGY SUBMITTAL.
 CEILING INSULATION ON PLAN PAGE A-1 IS LISTED AS R-19.
 WHAT TYPE OF INSULATION WILL BE INSTALLED?
 STATE THE EXT. WALL INSULATION TYPE AND R-VALUE ON
 PLAN.
 FBC 107.3.5.1.6 ENERGY CALCULATIONS ? PROVIDE AN ENERGY
 SUBMITTAL COMPLIANT WITH FBC-E 103;
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
 FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE
 ALTERNATIVE.
 R405.2 EC.
  
 4. REFERENCE PAGE C-1 FOR THE FOLLOWING:
 BUILDING DATA: NEW A/C AREA IS STATED AS 224 SF.
 (PATIO/PORCH)
 WILL THE GARAGE CONVERSION BE CONDITIONED SPACE?
 PLEASE CLARIFY?
  
 5.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE
 R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
  
 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN
 PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 7. REFERENCE PLAN PAGE A-8 FOR THE FOLLOWING:
 ELEVATION VIEWS APPEAR TO BE A MIRROR IMAGE OF THE
 FLOOR PLAN. PLEASE CLARIFY?
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  