Date |
Text |
2022-02-01 12:58:52 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21110389 |
| ADD: 2450 PRESIDENTIAL WAY # 607 |
| CONT: J & M CONTRACTORS OF S FLORIDA |
| TEL: 561-718-7040 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. FEB. 01/2022 |
| ACTION: DENIED |
| |
| 1) SHEET A-1: |
| 1A-F) COMPLIED |
| |
| 1G) THE FLOOR PLAN NOW STATES THE FLOOR UNDERLAYMENT TO |
| BE INSTALLED IS PROFLEX 90 MSC. THE CITY HAS NEVER SEEN |
| THE PRODUCT PROFLEX 90 MSC TESTED FOR A 6 INCH CONCRETE |
| SLAB FOR EITHER MARBLE OR TILE. |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE, VINYL LAMINATE FLOORING AND WOOD |
| FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT |
| TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND |
| MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE |
| STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO |
| DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 1G)(1) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 1G)(2) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 1G)(3) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 2) 2ND REQUEST. THERE ARE 3 DIFFERENT CONTRACTORS FROM |
| 3 DIFFERENT TRADES, A GENERAL CONTRACTOR, ELECTRICAL |
| CONTRACTOR AND PLUMBING CONTRACTOR EACH TAKING |
| RESPONSIBILITY FOR THE ONE SUBMITTED SHEET. |
| |
| FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| ONE SHEET |
| |
| 1ST ROUND OF COMMENTS. CERTIFICATION BY CONTRACTOR. |
| 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| LICENSED IN AND PLANS DRAWN. |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| AND PLANS DRAWN. |
| FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| ONE SHEET. |
| |
| |
| 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |