Plan Review Notes For Permit 21110387 |
Permit Number |
21110387 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-21 10:21:39 | ELECTRICAL PLAN REVIEW FAILED | | 1) PLEASE CHANGE ALL REFERENCES TO NEC 2020 CODE TO THE | | CURRENTLY ADOPTED 2017 NEC | | 2) PLEASE ENSURE ALL APPLICABLE 120-VOLT CIRCUITS | | COMPLY WITH ARC FAULT PROTECTION AS OTLINED IN NEC | | 210.12. A NOTE WILL SUFFICE | | 3) VERIFY VALUE OF ELECTRICAL ALTERATION AS PER WPB | | AMENDMENT 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|