Plan Review Notes
Plan Review Notes For Permit 21110387
Permit Number 21110387
Review Stop E
Sequence Number 1
Notes
Date Text
2021-12-21 10:21:39ELECTRICAL PLAN REVIEW FAILED
 1) PLEASE CHANGE ALL REFERENCES TO NEC 2020 CODE TO THE
 CURRENTLY ADOPTED 2017 NEC
 2) PLEASE ENSURE ALL APPLICABLE 120-VOLT CIRCUITS
 COMPLY WITH ARC FAULT PROTECTION AS OTLINED IN NEC
 210.12. A NOTE WILL SUFFICE
 3) VERIFY VALUE OF ELECTRICAL ALTERATION AS PER WPB
 AMENDMENT 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.