Plan Review Notes
Plan Review Notes For Permit 21110254
Permit Number 21110254
Review Stop B
Sequence Number 3
Notes
Date Text
2022-03-08 12:04:57JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL33818-R2(HVHZ), PROVIDE THE FOLLOWING INFORMATION:
 SELECT PRODUCT TO BE USED FROM EVALUATION REPORT PAGES
 1-4; SELECT FASTENING DETAILS TO BE USED FROM APPNDIX A
 PAGES 1-3; SELECT APPROVED SYSTEM NO. TO BE USED FROM
 APPNDIX B PAGES 1-4; SELECT EXPOSURE, BUILDING TYPE,
 ZONE, MEAN ROOF HEIGHT & RISK CATEGORY FROM APPENDIX C
 PAGES 1-3. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 2. SUBMITTED PRODUCT APPROVAL FL17206-R4 HAS BEEN
 REVISED TO FL17206-R5. PLEASE PROVIDE A COMPLETE SET.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3. THIRD REQUEST.
 3. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 ROOF HEIGHT. THIRD REQUEST.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  