2021-12-01 06:59:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21110246 |
| ADD: 2450 PRESIDENTIAL WAY # 1707 |
| PCN:74-43-43-18-10-000-1707 |
| CONT: WRIGHT?S IMPACT WINDOW & DOOR LLC |
| TEL: 561-588-7353 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: WED. DEC.01ST/ 2021 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. THE WRIGHT?S FLOOR PLAN & OPENING |
| SCHEDULE NEEDS TO SHOW WHO THE AUTHOR IS OF THE PLAN. |
| CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR |
| (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL |
| NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. |
| PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE |
| NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS |
| DRAWN. |
| |
| 2) 2ND REQUEST. DRAWING 1 WRIGHT?S FLOOR PLAN DOES NOT |
| SHOW THE FLOOR PLAN IN THE OVERALL CURVATURE OF THE |
| BUILDING, NOR THE UNITS THAT ARE PROJECTED FURTHER OUT |
| THAN OTHER PORTIONS OF THE WALL LINE. ENGINEERING |
| EXPRESS SHEET SHOWS FOR COMPLEX BUILDINGS USE CORNER |
| ZONES IF AT ALL IN QUESTION. WITH THE CURVATURE OF THE |
| BUILDING AND OFFSET WALL SECTIONS FOR BOTH SIDES OF THE |
| BUILDING IT WOULD CREATE SMALL VORTEX POCKETS WHERE THE |
| BALCONIES ARE DROPPED BACK IN FROM THE FRONT OF THE |
| BUILDING. THIS WILL GREATLY AFFECT THE PRESSURES ON |
| THESE OPENINGS AND SUBMITTED SCHEDULE. |
| BUILDING END ZONES (5). THE FLOOR PLAN LAYOUT INDICATES |
| THE WORK TO BE PERFORMED UNDER THIS PERMIT IS A CORNER |
| UNIT OF A HIGHRISE BUILDING. THE WIND LOAD CHART UNDER |
| NOTES STATES WHAT IS CONSIDERED AN END ZONE 10% OF THE |
| LEAST HORIZONTAL DISTANCE OF THE BUILDING OR 40% OF THE |
| MRH, BUT NOT LESS THAN 4% OF THE LEAST HORIZONTAL |
| DISTANCE OR 3 FT. THE CONTRACTOR HAS NOT IDENTIFIED |
| WHAT THE LEAST HORIZONTAL DISTANCE IS FOR THE BUILDING |
| NOR THE LOCATION OF THE UNIT IN RELATIONSHIP TO THE |
| BUILDING AND THE INTERCOASTAL WATERWAY. EXAMPLE ONLY. |
| IF THE BUILDING HEIGHT IS APPROXIMATELY 180 FT. (MRH.) |
| X 0.40= 72 FEET. THIS WOULD PUT ALL OPENINGS IN WIND |
| ZONE 5 OR 10% OF THE LEAST HORIZONTAL DISTANCE OF THE |
| BUILDING, ALSO UNKNOWN. |
| |
| 3) THE REVIEW OF THE SUBMITTED PRODUCT APPROVALS CANNOT |
| OCCUR WITH ALL OF THE UNKNOWNS LISTED IN COMMENT 2. |
| |
| 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |