Plan Review Notes
Plan Review Notes For Permit 21110245
Permit Number 21110245
Review Stop B
Sequence Number 2
Notes
Date Text
2021-12-13 16:33:22PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, ITEM # 2 OF THE LAST REVIEW STILL LEAVES
 SOME UNANSWERED QUESTIONS AS PER COMMENTS BELOW:
  
 A.) SLIDING GLASS DOOR AT OPENING #3 APPEARS TO BE IN A
 ZONE 5 AREA AS IT IS CLEARLY CLOSE TO THE EDGE OF THE
 WALL.
 B.) PLEASE CONFIRM THAT THE CURVATURE OF THE BUILDING
 HAS BEEN TAKEN INTO CONSIDERATION IN CALCULATING THE
 DESIGN WIND PRESSURES AND THAT ALL WINDOW/DOOR
 LOCATIONS ARE NOT IN ZONE 5.
  
  