2022-01-20 10:35:01 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) [NOT ADDRESSED. THE MANUFACTURE'S AND OR SHOP |
| DRAWINGS ARE REQUIRED IN ORDER TO DETERMINE IF THE |
| GENERATORS WILL COMPLY WITH THE FLORIDA BUILDING CODE |
| FOR WINDLOADING, SOUND AND OTHER REQUIREMENTS. THE |
| DETAILS OF HOW THE GENERATORS WILL BE ATTACHED TO THE |
| EXISTING SLABS IS ALSO REQUIRED. THIS INFORMATION IS |
| REQUIRED BEFORE THE PERMIT CAN BE ISSUED AND CAN NOT BE |
| DEFERRED.] SUBMIT SHOP DRAWINGS THAT DETAIL EQUIPMENT |
| ASSEMBLIES AND INDICATE DIMENSIONS, WEIGHTS, LOADS, |
| REQUIRED CLEARANCES, METHOD OF FIELD ASSEMBLY, |
| COMPONENTS, AND LOCATION AND SIZE OF EACH FIELD |
| CONNECTION. |
| A) DIMENSIONED OUTLINE PLAN AND ELEVATION DRAWINGS OF |
| ENGINE-GENERATOR SET AND OTHER COMPONENTS SPECIFIED. |
| B) VIBRATION ISOLATION BASE DETAILS: DETAIL |
| FABRICATION, INCLUDING ANCHORAGES AND ATTACHMENTS TO |
| STRUCTURE AND TO SUPPORTED EQUIPMENT. INCLUDE WEIGHTS. |
| SHOW THAT ANCHORING WILL RESIST WINDLOADS ON EQUIPMENT. |
| |
| 2) [THE LETTER RESPONCE LETTER STATES THAT ALL OF THE |
| GENERATORS ARE LOCATED MORE THAN 10 FEET FROM THE |
| BUILDINGS. THIS NEEDS TO BE STATED ON THE SITE PLAN OR |
| SURVEY.] THE GENERATOR EXHAUST IS REQUIRED TO BE AT |
| LEAST 10 FEET FROM ANY OPENINGS INTO A BUILDING. |
| R303.5.1 INTAKE OPENINGS. |
| MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS |
| SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM |
| ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, |
| CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS |
| AND LOADING DOCKS. |
| |
| 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |