Plan Review Notes
Plan Review Notes For Permit 21110234
Permit Number 21110234
Review Stop E
Sequence Number 1
Notes
Date Text
2021-12-20 12:57:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE PROVIDE CUT SHEETS FOR THE GENERATORS, AND
 TRANSFER SWITCHES. ARE THE ALL THE SAME SIZE? 110.3
  
 WHAT LOADS ARE BEING FED BY GENERATOR, PLEASE PROVIDE A
 PANEL SCHEDUULE. 215.5