2021-12-14 08:05:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT SHOP DRAWINGS THAT DETAIL EQUIPMENT
 ASSEMBLIES AND INDICATE DIMENSIONS, WEIGHTS, LOADS,
 REQUIRED CLEARANCES, METHOD OF FIELD ASSEMBLY,
 COMPONENTS, AND LOCATION AND SIZE OF EACH FIELD
 CONNECTION.
 A) DIMENSIONED OUTLINE PLAN AND ELEVATION DRAWINGS OF
 ENGINE-GENERATOR SET AND OTHER COMPONENTS SPECIFIED.
 B) VIBRATION ISOLATION BASE DETAILS: DETAIL
 FABRICATION, INCLUDING ANCHORAGES AND ATTACHMENTS TO
 STRUCTURE AND TO SUPPORTED EQUIPMENT. INCLUDE WEIGHTS.
 SHOW THAT ANCHORING WILL RESIST WINDLOADS ON EQUIPMENT.
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  