Plan Review Notes For Permit 21110204 |
Permit Number |
21110204 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-23 13:26:59 | NEW GUARD HOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) ALL PRODUCT APPROVALS (WINDOWS, DOORS, ROOFING | | SYSTEM ETC.) NEED TO BE REVIEWED AND MARKED APPROVED BY | | THE BUILDING DESIGNER OF RECORD - FBC WPB 107.3.4 | | | | 2) PLEASE SHOW ATTIC ACCESS OPENING DIMENSIONS PER FBC | | 1209.2 ATTIC SPACES. | | AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM | | BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A | | CLEAR HEIGHT OF OVER 30 INCHES (762 MM). CLEAR HEADROOM | | OF NOT LESS THAN 30 INCHES (762 MM) SHALL BE PROVIDED | | IN THE ATTIC SPACE AT OR ABOVE THE ACCESS OPENING. | | | | 3) PLEASE SHOW THE ROOF TILE ATTACHMENT TYPE - CIRCLE | | THE ATTACHMENT TYPE ON THE PROVIDED PRODUCT APPROVAL - | | IF USING ADHESIVE PLEASE PROVIDE THE PRODUCT APPROVAL | | FOR THE ADHESIVE AND THE UNDERLAYMENT SYSTEM - FBC WPB | | 107.2.1.1 | | | | 4) SEPARATE PERMIT REQUIRED FOR THE SITEWALL/FENCE. |
|