Plan Review Notes
Plan Review Notes For Permit 21110176
Permit Number 21110176
Review Stop B
Sequence Number 1
Notes
Date Text
2022-02-24 13:38:59BUILDING AUDIT FOR PERMIT #21110176
 PRIVATE PROVIDER
 SEC. 553.791 F.S.
  
 NEW SINGLE FAMILY RESIDENCE
 CODE IN EFFECT: FBC-RESIDENTIAL,7TH EDITION, 2020.
  
 1- ROOF SHEATHING NAILING SPACING SPECIFIED ON SHEET
 S-2 DOESN'T COMPLY WITH TABLE R803.2.3.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 2- GABLE END UPLIFT DIAGRAM SHOWN ON SHEET S-2 DOESN'T
 MATCH ROOF ZONES ZONES SPECIFIED ON FIGURE R301.2(7)
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 3- PLANS DON'T PROVIDE SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR
 ROOFING UNDERLAYMENT SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001
  
 4-STUCCO SPECIFICATIONS ON THE TYPICAL GABLE END DETAIL
 AND WALL SECTIONS ON SHEET A-3 DON'T COMPLY WITH SEC.
 R703.7.3 FBC-RESIDENTIAL. NEED TO SPECIFY TWO WATER
 RESISTIVE BARRIERS WHEN STUCCO IS APPLIED TO WOOD.
  
 5- WIND DESIGN INFORMATION ON SHEET A-1 IS NOT CLEAR.
 ULTIMATE WIND SPEED AND NOMINAL WIND SPEED UNDER WALL
 PRESSURES DON'T MATCH THE ULTIMATE WIND SPEED AND
 NOMINAL WIND SPEED UNDER WIND DESIGN BASIS SHOWN ON THE
 SAME SHEET. REVISE/CLARIFY AS REQUIRED. WHICH ONE IS
 THE CORRECT DESIGN CRITERIA FOR THIS HOUSE? SEC.
 R301.2.1 FBC-RESIDENTIAL.
 NOTE: REVISE WINDOWS/DOORS DESIGN PRESSURES ACCORDINGLY
 TO AVOID CONFLICTS/DELAYS.
  
 6- ENERGY CALCULATIONS:
 A)ROOF TYPE SPECIFIED ON PAGE 2 DOESN'T MATCH PLANS.
 THIS IS A HIP ROOF. REVISE AS REQUIRED. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B)DOOR INFORMATION SPECIFIED ON PAGE 3 DOESN'T MATCH
 PLANS AND PRODUCT APPROVALS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED. THERE IS
 NOT INSULATED DOOR ON THE SOUTH SIDE. THIS IS A
 METAL/GLASS FRENCH DOOR. NOTE: GLAZING IN DOORS NEEDS
 TO BE INCLUDED IN THE WINDOW GLAZING AREA. SEE SEC.
 R405.5.3 FBC-ENERGY CONSERVATION.
  
 C)E) WINDOW OVERHANG DEPTH AND SEPARATION INFORMATION
 SHOWN ON PAGE 3 DOESN'T MATCH PLANS. SEC. R101.5.1.1.2
 FBC-. ENERGY CONSERVATION. REVISE AS REQUIRED TO MATCH.
  
 D)WINDOW AREA SHOWN ON PAGE 3 DOESN'T MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-. ENERGY CONSERVATION. REVISE AS
 REQUIRED TO MATCH.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  