Plan Review Notes
Plan Review Notes For Permit 21110174
Permit Number 21110174
Review Stop B
Sequence Number 2
Notes
Date Text
2022-01-20 15:15:16PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, THE PLANS DO NOT SHOW THE DESIGN WIND
 SPEED AND THE ENGINEER?S LETTER INDICATES A DESIGN WIND
 SPEED OF 150 MPH. THIS SHOULD BE 170 MPH.
  
 PLEASE CORRECT THE WIND SPEED SHOWN ON PLAN SHEET 001
 TO MATCH WITH THE SUBMITTED STRUCTURAL CALCULATIONS.
  
  