Plan Review Notes For Permit 21110174 |
Permit Number |
21110174 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-01-20 15:15:16 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, THE PLANS DO NOT SHOW THE DESIGN WIND | | SPEED AND THE ENGINEER?S LETTER INDICATES A DESIGN WIND | | SPEED OF 150 MPH. THIS SHOULD BE 170 MPH. | | | | PLEASE CORRECT THE WIND SPEED SHOWN ON PLAN SHEET 001 | | TO MATCH WITH THE SUBMITTED STRUCTURAL CALCULATIONS. | | | | |
|