2022-03-16 11:22:41 | 3RD REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21110157 |
| 3/16/2022 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| 1ST REVIEW AND 2ND REVIEW ARE LISTED BELOW WITH |
| ADDITIONAL NOTES. PLEASE COMPLY WITH THE COMMENTS AND |
| NOTES. |
| |
| 4) FAILED. P2.1: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE REGULATORS, THE COOKING APPLIANCES, AND THE GAS |
| WATER HEATER- SECTIONS 410.2, 623.1, AND 624.1 FBC FG. |
| THE RANGE SUBMITTAL INDICATES THE APPLIANCE HAS A |
| 280,000 BTU LOAD HOWEVER THE RISER INDICATES 70,000 |
| BTU. PLEASE CORRECT THE RISER DRAWING ACCORDINGLY. |
| |
| 5) FAILED. P2.1: PROVIDE COMBUSTION AIR CALCULATIONS |
| FOR THE COOKING APPLIANCES AND INDICATE HOW THE AIR |
| WILL BE SUPPLIED- SECTION 304.1 FBC FG. NOT PROVIDED. |
| THE NARRATIVE RESPONSE REFERENCES THE CAPTIVE AIRE |
| DRAWINGS HOWEVER MAKE-UP AIR FOR HOOD EEXHAUST IS NOT |
| COMBUSTION AIR FOR APPLLIANCES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |