Plan Review Notes
Plan Review Notes For Permit 21110157
Permit Number 21110157
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-02-22 10:41:21FIRE PROVISO COMMENT:
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B IN ALL CORRIDORS AND LOBBIES AND
 CLASS A, CLASS B, OR CLASS C IN ALL GENERAL ASSEMBLY
 AREAS FOR WALLS AND CEILING. NFPA 101 12.3.3 THE
 INTERIOR FLOOR FINISH SHALL COMPLY WITH NFPA 101 10.2
  