2021-11-30 13:47:55 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21101057 |
| 11/30/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A1.00 & P0.1: PROVIDE PLUMBING FIXTURE |
| CALCULATIONS FOR THE NEW RESTAURANT IN COMPLIANCE WITH |
| TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT INDICATES |
| THE REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES. |
| BASED ON THE TABLE AND THE OCCUPANT LOAD OF 240 |
| PERSONS, THE PLANS APPEAR TO SHOW A DEFICIENCY OF 1 |
| MALE WATER CLOSET AND 1 FEMALE WATER CLOSET. PLEASE |
| NOTE DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR |
| RESTAURANTS UNLESS WATER WILL BE SERVED IN CONTAINERS |
| FREE OF CHARGE IN ACCORDANCE WITH SECTION 410.4 FBC P. |
| PLEASE REVISE THE PLANS TO INDICATE WHICH METHOD WILL |
| BE USED AND ALSO TO SHOW THE ADDITION MALE AND FEMALE |
| WATER CLOSETS- SECTION 107.2.1 WPB. |
| |
| 2) A3.00: FBC- 2020 ACCESSIBILITY COMPLIANCES: |
| A) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE |
| WATER CLOSETS- SECTION 604.3. |
| B) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE |
| LAVATORIES- 606.2. |
| C) TURNING SPACE DIAMETERS- 304.3. |
| D) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAM BEYOND |
| THE ARC OF THE DOOR- 603.2.3 |
| E) HEIGHTS OF THE WATER CLOSET SEATS (NOT THE RIMS OF |
| THE BOWLS) FROM THE FINISHED FLOORS- SECTION 604.4. |
| F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACES- 603.3. THE DETAIL SHOWS THE |
| MEASUREMENT TO THE BOTTOM OF MIRROR FRAME. |
| G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF THE GRAB |
| BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| FIGURES 604.5.1 & 604.5.2. ADD A NOTE TO THE SIDE BAR |
| GRAB BAR TO INDICATE IT SHALL EXTEND A MINIMUM OF 54 |
| INCHES FROM THE REAR WALL. SHOW THE REAR GRAB WILL |
| EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12 |
| INCHES TOWARDS THE SIDE WALL AND 24 INCHES ON THE OTHER |
| SIDE. |
| H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- 604.6. |
| I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| FIGURE 604.7. |
| J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- 606.2 |
| AND FIGURES 306.2 & 306.3. |
| |
| 2) A3.00: PLEASE INDICATE THE WALL SURROUND FINISH |
| MATERIALS TO BE INSTALLED IN THE BATHROOMS AND AT THE |
| MOP SINK- SECTION 310.3 FBC P AND 1210.2.2 FBC B- WALLS |
| AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS |
| AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL |
| ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF |
| A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| |
| 3) P0.1 & A1.01: THE GREASE INTERCEPTOR CALCULATIONS ON |
| P0.1 INDICATE 70 SEATS HOWEVER 160 SEATS ARE INDICATED |
| ON A1.01. PLEASE REVISE THE CALCULATIONS- SECTION |
| 1003.3 FBC P. BASED ON THE FORMULA USED THE REQUIRED |
| INTERCEPTOR CAPACITY IS 1920 GALLONS. SPECIFICATIONS |
| FOR THE GB-250 INDICATE THE INTERCEPTORS ARE UNDERSIZED |
| FOR THE LOAD- GREASE RETENTION CAPACITY IS BASED ON |
| 100/200 GPM FLOW WITH 200 GPM BEING THE MAXIMUM OF EACH |
| OF THE 3 INTERCEPTORS. |
| |
| 4) P1.1 & P2.1: THE CLEAR WATER WASTE FROM THE HAND |
| SINK, WALK-IN COOLER EVAPORATOR AND THE ICE MACHINE |
| SHALL NOT DRAIN INTO THE GREASE WASTE LINE AND |
| INTERCEPTOR- SECTION 1003.3.1 FBC P. THE CONDENSATE |
| FROM THE EVAPORATOR IS ALSO RESTRICTED FROM DRAINING |
| INTO THE SANITARY SYSTEM AND SHALL BE DISCHARGED TO AN |
| APPROVED LOCATION SUCH AS THE STORM DRAIN SYSTEM OR |
| DRYWELL- SEC. 90-126 WPB CODE OF ORDINANCES. |
| |
| 5) P1.1 & P2.1: SHOW DRAINAGE AND VENT PIPING FOR THE |
| UNDERCOUNTER DISHWASHER- SECTION 1003.3.1 FBC P. |
| |
| 6) P1.1 & P2.1: SHOW THE WATER LINE CONNECTIONS TO THE |
| UNDERCOUNTER DISHWASHER, BEVERAGE DISPENSERS, COFFEE |
| BREWER, EXPRESSO MACHINE ETC.- SECTION 107.2.1 WPB. |
| CLARIFY IF A WATER FILTERING SYSTEM WILL BE INSTALLED |
| AND ADD IT TO THE DRAWINGS AND EQUIPMENT SCHEDULE IF |
| APPLICABLE. |
| |
| 7) P1.1 & P2.1: SHOW THE LOCATIONS OF REQUIRED BACKFLOW |
| PREVENTERS FOR WATER LINE CONNECTIONS TO THE |
| DISHWASHERS, BEVERAGE DISPENSERS, COFFEE BREWER, |
| EXPRESSO MACHINE, WATER FILTER ETC.- SECTION 608.3 FBC |
| P. PLEASE INCLUDE A DEVICE SCHEDULE INDICATING MAKES, |
| MODELS AND COMPLIANCE STANDARDS. |
| |
| 8) P120: PROVIDE WATER HAMMER ARRESTOR SYMBOLS ON THE |
| WATER ISOMETRIC DRAWING- SECTION 604.9 FBC P. |
| |
| 9) P120: PROVIDE AN ENLARGED WATER FILTER PIPING |
| DRAWING (IF INSTALLED) INDICATING COMPLIANCE WITH |
| SECTIONS 608.3 & 608.4 FBC P. |
| |
| 10) P120: THE PLAN SHOWS NON-COMPLIANCE WITH SECTION & |
| TABLE C404.5.1 FBC EC. A 1/2 INCH HW PIPE HAS A MAXIMUM |
| ALLOWABLE LENGTH OF 2 FT. FROM THE NEAREST HOT WATER |
| SOURCE TO THE FIXTURE SUPPLY PIPE AT THE LAVATORIES. |
| PLEASE PROVIDE EITHER POINT OF USE WATER HEATERS AT THE |
| LAVATORIES OR A HOT WATER RECIRCULATION PUMP. |
| |
| 11) P0.1: PLEASE PROVIDE A PLUMBING FIXTURE SCHEDULE OR |
| INDICATE WHICH FIXTURES WILL BE DEFERRED SUBMITTALS- |
| SECTION 107.1 & 107.3.4.1 WPB. CLARIFY IF THE WATER |
| CLOSETS WILL BE FLUSH TANKS OR FLUSH VALVES- SEE TABLE |
| 604.3 FBC P. |
| |
| 12) ENERGYGAUGE COMPLIANCE FORM: INCORRECT COMPLIANCE |
| DATA FOR THE WATER HEATER AND WATER PIPING HAS BEEN |
| ENTERED. THE WATER HEATER IS GAS, NOT ELECTRIC, HW |
| TEMPERATURE IS HIGHER THAN 105 DEGREES F, PIPING IS |
| LARGER THAN 0.25. PLEASE SEE SECTION C404.1 FBC EC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |