Plan Review Notes For Permit 21110157 |
Permit Number |
21110157 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-11-30 15:01:58 | 1ST REVIEW FBC-2020 FUEL GAS | | PERMIT- 21110157 | | 11/30/21 | | | | CODES IN EFFECT: | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P2.1: PLEASE INCLUDE THE 199,900-WATER HEATER | | BTU?S TO THE TOTAL GAS CONSUMPTION TABLE- SECTION 402.2 | | FBC FG. | | | | 2) P2.1: INDICATE THE SIZE OF THE SUPPLY PIPE FROM THE | | REGULATOR TO THE WATER HEATER- SECTION 402.3 FBC FG. | | | | 3) P2.1: SHOW PIPE UNIONS WITHIN 1 FT. OF EACH SIDE OF | | THE REGULATORS IN ACCORDANCE WITH SECTION 410.2 (7) FBC | | FG. | | | | 4) P2.1: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | REGULATORS, THE COOKING APPLIANCES, AND THE GAS WATER | | HEATER- SECTIONS 410.2, 623.1, AND 624.1 FBC FG. | | | | 5) P2.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | COOKING APPLIANCES AND INDICATE HOW THE AIR WILL BE | | SUPPLIED- SECTION 304.1 FBC FG | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|