Plan Review Notes For Permit 21110157 |
Permit Number |
21110157 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-11-12 13:43:35 | PROVIDE RAMP DIMENSIONS/DETAILS FOR 2ND EXIT. NFPA 101 | | 7.2.5 | | PROVIDE EXIT PASSAGEWAY WIDTH FOR 2ND EXIT INCLUDING | | CAPACITY. NFPA 101 7.2.6.4 | | PROVIDE EXIT DOOR HARDWARE TO BE INSTALLED. NFPA 101 | | 12.2.2.2 | | INDICATE ON PLAN EMERGENCY LIGHTING LOCATIONS. NFPA 101 | | 12.2.9 | | INDICATE ON PLAN LOCATION OF EXIT SIGNAGE. NFPA 101 | | 12.2.10 | | COMMERCIAL COOKING/SUPPRESSION TO BE SUBMITTED UNDER A | | SEPARATE PERMIT. NFPA 101 12.3.2.2, NFPA 1 50.2.1 | | IDENTIFY INTERIOR FINISHES THAT COMPLY WITH NFPA 101 | | 12.3.3 | | ANY FIRE SPRINKLER CHANGES/MODIFICATIONS TO BE | | SUBMITTED UNDER A SEPARATE PERMIT. | | |
|