Plan Review Notes
Plan Review Notes For Permit 21110147
Permit Number 21110147
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-11-15 16:30:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF EXTENSIVE REPIAR WORK
 THAT MAY AFFECT THE FIRE ALARM(FA), FIRE SPRINKLER(FS)
 AND EXITING.
  
 PLEASE PROVIDE GREATER DETAIL IF THE BUILDING IS TO
 REPAIR OCCUPIED DURING THIS PROPOSED WORK.
  
 PLEASE PROVIDE A LIFE SAFETY REVIEW OF THE EXITING,
 EXIT DETOURS, PROTECTION FRORM FALLING DEBRIS.
  
 INCLUDE A NOTE THE FS & FA WILL BE MAINTAINED
 THROUGHTOUT THE PORJECT THAT ALL WORK ON THE FS & FA
 WORK WILL BE DONE UNDER SEPARATE PERMITS AND SHOP
 DRAWINGS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  