Plan Review Notes
Plan Review Notes For Permit 21110114
Permit Number 21110114
Review Stop B
Sequence Number 1
Notes
Date Text
2021-11-03 12:23:43JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. PLEASE CLARIFY & PROVIDE THE
 FOLLOWING INFORMATION FOR MIAMI-DADE NOA NO.:
 20-0110.11 FOR THE PROPOSED FLAT ROOF SYSTEM TO BE USED
 CORRESPONDING TO THE SUBMITTED ENGINEERS CALCULATIONS.
 COVER PAGE, EVALUATION REPORTS, LIMITATIONS PAGE AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. IF USING
 SUBMITTED PRODUCT APPROVAL FL2533-R26 PROVIDE
 EVALUATION REPORT PAGES 1-5 TO INCLUDE LIMITATION PAGE.
 2. SUBMITTED PRODUCT APPROVAL FL9777-R13 HAS BEEN
 REVISED TO FL9777-R15. PLEASE PROVIDE A COMPLETE SET.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER
 RULE 61G20-3.
 3. INSPECTION WAIVERS/ROOFING AFFIDAVITS ARE NOT A PART
 OF PLAN REVIEW. ALL INSPECTION MATTERS MUST BE ADDRESS
 BY YOUR BUILDING INSPECTOR.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  