 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1 FBC R 301 FAC9N-3. SUBMITTED ROOF
 SKETCH/DRAWING INDICATES REROOFING CRICKET AREA WHICH
 IS CONSIDERED A LOW ROOF SLOPE AREA. SUBMITTED
 MIAMI-DADE COUNTY NOA NO. 17-1004.09 SYSTEM TYPE E(5)
 WITH A MAXIMUM DESIGN PRESSURE -52.5 DO NOT MEET THE
 MINIMUM DESIGN PRESSURE REQUIREMENT FOR AN EXPOSURE C
 CATEGORY AREA OF -108.17 AND WILL REQUIRE SIGNED AND
 SEALED ENGINEERED DESIGN PRESSURE CALCULATIONS BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT, OR REGISTERED ROOF CONSULTANT AS PER
 LIMITATION #7.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  