Plan Review Notes For Permit 21110043 |
Permit Number |
21110043 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-11-15 09:49:21 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | 1. FBC B 107.2.1 FBC R 301 FAC9N-3. SUBMITTED ROOF | | SKETCH/DRAWING INDICATES REROOFING CRICKET AREA WHICH | | IS CONSIDERED A LOW ROOF SLOPE AREA. SUBMITTED | | MIAMI-DADE COUNTY NOA NO. 17-1004.09 SYSTEM TYPE E(5) | | WITH A MAXIMUM DESIGN PRESSURE -52.5 DO NOT MEET THE | | MINIMUM DESIGN PRESSURE REQUIREMENT FOR AN EXPOSURE C | | CATEGORY AREA OF -108.17 AND WILL REQUIRE SIGNED AND | | SEALED ENGINEERED DESIGN PRESSURE CALCULATIONS BY A | | FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED | | ARCHITECT, OR REGISTERED ROOF CONSULTANT AS PER | | LIMITATION #7. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | |
|