Date |
Text |
2022-05-16 13:25:11 | RESIDENTIAL (R3) ALTERATION THIRD BUILDING AUDIT. |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21110017 (GUEST HOUSE) |
| |
| NOTE: |
| THIS IS A LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING |
| BUILDING. SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1- OK. |
| 2- OK. |
| |
| ORIGINAL COMMENT: |
| 3- SECOND FLOOR BEDROOM EGRESS WINDOWS DON'T SEEM |
| COMPLY WITH SEC. R310.2.1 FBC-RESIDENTIAL. REVISE AS |
| REQUIRED. SHOW COMPLIANCE WITH MIN. CLEAR OPENINGS |
| (WIDTH, HEIGHT AND TOTAL CLEAR OPENING). |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| UNABLE TO VERIFY EGRESS WINDOW. |
| |
| ORIGINAL COMMENT: |
| 4- PLANS DON'T PROVIDE ANY INFORMATION ABOUT SECOND |
| FLOOR WINDOW FALL PROTECTION. WINDOW FALL PROTECTION |
| SHALL BE PROVIDED ON SECOND FLOOR WINDOWS WHERE THE TOP |
| OF THE WINDOW SILL OF AN OPERABLE WINDOW IS LOCATED |
| LESS THAN 24" ABOVE THE FINISHED FLOOR . SEC. R312.2 |
| FBC RESIDENTIAL. |
| NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND |
| FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL |
| PROTECTION IF REQUIRED. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| UNABLE TO VERIFY IF WINDOW FALL PROTECTION IS REQUIRED |
| |
| ORIGINAL COMMENT: |
| 5- PLANS DON'T PROVIDE ANY INFORMATION FOR THE NEW |
| SPIRAL STAIR. |
| UNABLE TO CHECK EGRESS. SEC. R311.7.10.1 |
| FBC-RESIDENTIAL. SPECIFY STAIR SIZE AND TREAD AND |
| RISERS DIMENSIONS. PROVIDE COMPLETE |
| DETAILS/SPECIFICATIONS FOR CONSTRUCTION: FOOTING, |
| ANCHORING, ETC. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| PLANS DON'T SPECIFY SIZE OF SPIRAL STAIR. UNABLE TO |
| VERIFY EGRESS. |
| ALSO, DETAIL 1 ON SHEET A3.20 DOESN'T SPECIFY THE |
| HEIGHT OF THE HANDRAIL AND IT LOOKS LIKE THE STAIR |
| HANDRAIL PICKETS SPACING DON'T COMPLY WITH THE OPENING |
| LIMITATIONS OF SEC. R312.1.3 FBC-RESIDENTIAL. |
| |
| 6- OK. |
| 7- OK. |
| 8- OK. |
| |
| ORIGINAL COMMENT: |
| 9- PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| THE CONSTRUCTION AND INSTALLATION OF NEW CANVAS AWNINGS |
| AS SHOWN ON THE EAST ELEVATION. PROVIDE COMPLETE |
| DETAILS/SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| TYPICAL AWING DETAIL ON SHEET A3.20 DOESN'T PROVIDE |
| FASTENING SPECIFICATIONS. DESIGNER OF RECORD TO PROVIDE |
| THE INFORMATION TO SHOW COMPLIANCE WITH WIND DESIGN. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 10- OK. |
| 11- OK. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE AUDIT PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |