2021-12-16 17:57:41 | RESIDENTIAL (R3) ALTERATION BUILDING AUDIT. |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21110017 |
| |
| NOTE: |
| THIS IS A LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING |
| BUILDING. SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1- PLANS DON'T SPECIFY CURRENT CODE AND THE DESIGN |
| CRITERIA. SEC. 107.3.5.3 CITY AMENDMENTS. |
| ARCHITECT TO PROVIDE ALL THE WIND DESIGN CRITERIA AS |
| REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE |
| ULTIMATE AND NOMINAL WIND LOAD, BUILDING EXPOSURE, |
| BUILDING MEAN ROOF HEIGHTT. ALSO, SPECIFY THE |
| COMPONENTS AND CLADDING DESIGN PRESSURES FOR DOORS AND |
| WINDOWS. |
| |
| 2- PLANS DON'T PROVIDE ANY STRUCTURAL |
| DETAILS/SPECIFICATIONS. ARCHITECT NEEDS TO PROVIDE |
| COMPLETE INFORMATION AS REQUIRED BY SEC. SEC. 107.3.5.3 |
| CITY AMENDMENTS AND SEC. R301.1 FBC-RESIDENTIAL: |
| |
| A) PROVIDE COMPLETE OPENING FRAMING |
| DETAILS/SPECIFICATIONS FOR NEW WINDOWS AND DOORS. |
| SPECIFY ALL FRAMING MEMBERS SIZES AND CONNECTORS AT |
| EACH END. |
| |
| B) PROVIDE COMPLETE FRAMING DETAILS/SPECIFICATIONS FOR |
| NEW EXTERIOR WALLS AT NEW SPIRAL STAIR LOCATION AND |
| INFILL WALL SECTIONS ON AREAS SHOWN ON PLANS. SPECIFY |
| ALL FRAMING MEMBERS SIZES AND CONNECTORS AT EACH END. |
| |
| C)PROVIDE COMPLETE FRAMING DETAILS/SPECIFICATIONS AT |
| SECOND FLOOR OPENING FOR NEW SPIRAL STAIRS AND INFILL |
| FRAMING BY EXISTING STAIRCASE. SPECIFY ALL FRAMING |
| MEMBERS SIZES AND CONNECTORS AT EACH END. |
| |
| 3- SECOND FLOOR BEDROOM EGRESS WINDOWS DON'T SEEM |
| COMPLY WITH SEC. R310.2.1 FBC-RESIDENTIAL. REVISE AS |
| REQUIRED. SHOW COMPLIANCE WITH MIN. CLEAR OPENINGS |
| (WIDTH, HEIGHT AND TOTAL CLEAR OPENING). |
| |
| 4- PLANS DON'T PROVIDE ANY INFORMATION ABOUT SECOND |
| FLOOR WINDOW FALL PROTECTION. |
| WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND |
| FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN |
| OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE |
| FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL. |
| NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND |
| FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL |
| PROTECTION IF REQUIRED. |
| |
| 5- PLANS DON'T PROVIDE ANY INFORMATION FOR THE NEW |
| SPIRAL STAIR. |
| UNABLE TO CHECK EGRESS. SEC. R311.7.10.1 |
| FBC-RESIDENTIAL. SPECIFY STAIR SIZE AND TREAD AND |
| RISERS DIMENSIONS. PROVIDE COMPLETE |
| DETAILS/SPECIFICATIONS FOR CONSTRUCTION: FOOTING, |
| ANCHORING, ETC. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 6- PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| THE NEW SECOND FLOOR GUARDRAIL. |
| PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| CONSTRUCTION OF GUARDRAIL SHOWING COMPLIANCE WITH TABLE |
| R301.5, SEC. R312.1 FBC-RESIDENTIAL. |
| |
| 7- IT LOOKS LIKE WINDOW LOCATED ON THE SECOND FLOOR ON |
| THE WEST SIDE ADJACENT TO THE NEW BEDROOM CLOSET NEEDS |
| TO HAVE SAFETY GLAZING AS REQUIRED BY SEC. R308.4.2 |
| FBC-RESIDENTIAL. SHOW COMPLIANCE. |
| |
| 8-PROVIDE COMPLETE WALL SECTION SPECIFYING WALL |
| SHEATHING THICKNESS AND FASTENING, AND ALL EXTERIOR AND |
| INTERIOR FINISHES. SEC. 107..3.5.3 CITY AMENDMENTS. |
| ALSO, PROVIDE SPECIFICATIONS FOR THE REQUIRED TWO WATER |
| RESISTIVE BARRIERS WHEN STUCCO IS APPLIED TO WOOD AS |
| REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL. |
| |
| 9- PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| THE CONSTRUCTION AND INSTALLATION OF NEW CANVAS AWNINGS |
| AS SHOWN ON THE EAST ELEVATION. PROVIDE COMPLETE |
| DETAILS/SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| A)OUTSWING ENTRY DOOR AS SHOWN ON PLANS. |
| |
| 11-DESIGNER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| 12- WINDOW MULLIONS: NEITHER PLANS OR PRODUCT APPROVAL |
| SUBMITTED SPECIFY SIZE OF MULLIONS TO BE USED. SPECIFY |
| MULLIONS SIZE TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. |
| |