2022-05-16 11:20:14 | RESIDENTIAL (R3) ALTERATION THIRD BUILDING AUDIT. |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21110016 (MAIN HOUSE) |
| |
| NOTE: |
| THIS IS A LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING |
| BUILDING. SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE. |
| |
| 1-OK. |
| 2-OK. |
| |
| 3- NEW STAIRWAYS: |
| |
| ORIGINAL COMMENT: |
| A)PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE NEW STAIRWAYS SHOWING COMPLIANCE |
| WITH SEC. R11.7 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| (1) REPEAT COMMENT. NOT ADDRESSED. |
| EAST SIDE STAIRS: CLARIFY TREAD DIMENSIONS. FLOOR PLAN |
| SHOWS 48'-0" AND 96'-0" TREADS?. |
| (NOTE: SEE SHEET A1.10. ALSO, TO AVOID MORE CONFLICTS |
| AND UNNECESSARY DELAYS KEEP IN MIND THAT STAIRWAY |
| LANDING CAN NOT BE LESS THAN 36" AND READ SEC. R311.7.5 |
| FOR RISER AND TREAD REQUIREMENTS). |
| |
| (2)REPEAT COMMENT. NOT ADDRESSED. |
| WEST SIDE STAIRS: FLOOR PLAN DOESN'T PROVIDE DIMENSIONS |
| FOR LANDING AND TREADS. |
| (NOTE: SEE SHEET A1.10. ALSO, TO AVOID MORE CONFLICTS |
| AND UNNECESSARY DELAYS KEEP IN MIND THAT STAIRWAY |
| LANDING CAN NOT BE LESS THAN 36" AND READ SEC. R311.7.5 |
| FOR RISER AND TREAD REQUIREMENTS). |
| |
| 4- OK. |
| 5- OK. |
| 6- OK. |
| |
| ORIGINAL COMMENT: |
| 7- PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| THE CONSTRUCTION AND INSTALLATION OF NEW CANVAS AWNINGS |
| AS SHOWN ON THE EAST ELEVATION. PROVIDE COMPLETE |
| DETAILS/SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| TYPICAL AWING DETAIL ON SHEET A3.20 DOESN'T PROVIDE |
| FASTENING SPECIFICATIONS. DESIGNER OF RECORD TO PROVIDE |
| THE INFORMATION TO SHOW COMPLIANCE WITH WIND DESIGN. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| A)OK. |
| |
| ORIGINAL COMMENT: |
| B) INSWING FRENCH DOORS AS SHOWN ON PLANS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| ONLY PRODUCT APPROVAL FOR OUTSWING DOOR WAS SUBMITTED. |
| |
| 9- DESIGNER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT |
| APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 10- OK. |
| 11- OK. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE AUDIT PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |