2021-12-17 10:58:03 | RESIDENTIAL (R3) ALTERATION BUILDING AUDIT. |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21110016 |
| |
| NOTE: |
| THIS IS A LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING |
| BUILDING. SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE. |
| |
| 1-PLANS DON'T SPECIFY CURRENT CODE AND THE DESIGN |
| CRITERIA. SEC. 107.3.5.3 CITY AMENDMENTS. |
| ARCHITECT TO PROVIDE ALL THE WIND DESIGN CRITERIA AS |
| REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE |
| ULTIMATE AND NOMINAL WIND LOAD, BUILDING EXPOSURE, |
| BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE COMPONENTS |
| AND CLADDING DESIGN PRESSURES FOR DOORS AND WINDOWS. |
| |
| 2- PLANS DON'T PROVIDE ANY STRUCTURAL |
| DETAILS/SPECIFICATIONS. ARCHITECT NEEDS TO PROVIDE |
| COMPLETE INFORMATION AS REQUIRED BY SEC. SEC. 107.3.5.3 |
| CITY AMENDMENTS AND SEC. R301.1 FBC-RESIDENTIAL: |
| |
| A) PROVIDE COMPLETE OPENING FRAMING |
| DETAILS/SPECIFICATIONS FOR NEW WINDOWS AND DOORS. |
| SPECIFY ALL FRAMING MEMBERS SIZES AND CONNECTORS AT |
| EACH END. |
| |
| 3- NEW STAIRWAYS: |
| A)PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE NEW STAIRWAYS SHOWING COMPLIANCE |
| WITH SEC. R11.7 FBC-RESIDENTIAL. |
| |
| B)A LANDING COMPLYING WITH SEC. R311.3 FBC-RESIDENTIAL |
| IS REQUIRED IN THE STAIRWAY BY THE NEW DOUBLE FRENCH |
| DOORS. |
| |
| C) HANDRAIL IS REQUIRED ON THE NEW STAIRWAY BY THE NEW |
| DOUBLE FRENCH DOORS. |
| SEC. R311.7.8 FBC-RESIDENTIAL |
| |
| 4-PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| THE GUARDRAIL AND HANDRAIL. |
| PROVIDE COMPLETE DETAILS/SPECIFICATIONS SHOWING |
| COMPLIANCE WITH TABLE R301.5, SEC. R312.1 |
| FBC-RESIDENTIAL. |
| |
| 5- WINDOW ADJACENT TO THE SINGLE FRENCH DOOR NEEDS TO |
| HAVE SAFETY GLAZING AS REQUIRED BY SEC. R308.4.2 |
| FBC-RESIDENTIAL. SHOW COMPLIANCE. |
| |
| 6- PROVIDE COMPLETE WALL SECTION SPECIFYING WALL |
| SHEATHING THICKNESS AND FASTENING, AND ALL EXTERIOR AND |
| INTERIOR FINISHES. SEC. 107..3.5.3 CITY AMENDMENTS. |
| ALSO, PROVIDE SPECIFICATIONS FOR THE REQUIRED TWO WATER |
| RESISTIVE BARRIERS WHEN STUCCO IS APPLIED TO WOOD AS |
| REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL. |
| |
| 7- PLANS DON'T PROVIDE ANY DETAILS/SPECIFICATIONS FOR |
| THE CONSTRUCTION AND INSTALLATION OF NEW CANVAS AWNINGS |
| AS SHOWN ON PLANS. PROVIDE COMPLETE |
| DETAILS/SPECIFICATIONS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| A)OUTSWING ENTRY DOOR AS SHOWN ON PLANS. |
| |
| B) INSWING FRENCH DOORS AS SHOWN ON PLANS. |
| |
| 9- DESIGNER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| 10- MULLION: NEITHER PLANS OR PRODUCT APPROVAL |
| SUBMITTED SPECIFY SIZE OF MULLION TO BE USED BETWEEN |
| THE FRENCH DOOR AND THE WINDOW AS SHOWN ON PLANS. |
| SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 11- POOL AND POOL PAVERS ARE TO BE DONE UNDER SEPARATE |
| PERMITS. SEC. 105.1 CITY AMENDMENTS. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |