Plan Review Notes For Permit 21110011 |
Permit Number |
21110011 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2022-02-07 11:48:24 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | 1. SUBMITTED MIAMI-DADE COUNTY NOA 20-0131.01 COVERS | | MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(7). ALL | | APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY | | IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. SELECT | | SYSTEM TYPE TO BE USED. DETAILS AND ATTACHMENTS NOT | | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED | | SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED | | CALCULATIONS MAY BE REQUIRED; DEPENDENT UPON SYSTEM | | USED. PLEASE NOTE ADDRESS IS LOCATED IN AN EXPOSURE C | | CATEGORY AREA. SECOND REQUEST. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS | | |
|