Plan Review Notes For Permit 21101400 |
Permit Number |
21101400 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-04 12:51:08 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. THE PRODUCT APPROVAL IS NOT UPLOADED PROPERLY. THE | | SPEC SHEETS ARE NOT CLEAR AND ARE UPSIDE DOWN. FBC 107, | | WHEN UPLOADING PRODUCT APPROVALS ENSURE THAT THEY ARE | | UPLOADED IN THE CORRECT ORIENTATION TO FACILITATE PLAN | | REVIEW. | | | | 2. A DOCUMENT HAS BEEN UPLOADED TO YOUR FILE WHICH | | GIVES PRESCRIPTIVE WIND DESIGN LOADS FOR PALM BEACH | | COUNTY. YOU ARE PROPOSING A GARAGE DOOR THAT IS 8' X | | 7'. SEE THE WIND LOAD CHART; IT DOES NOT INCLUDE THE | | DOOR SIZE 8' X 7' SO YOU NEED TO USE THE NEXT SIZE | | WHICH IS 6' X 7'. | | | | THE DESIGN PRESSURE REQUIREMENTS FOR A 6' X 7' DOOR, | | EXPOSURE C, IS +39.8 / -50.6. THE DOOR PROPOSED HAS A | | DESIGN PRESSURE LIMITATION OF +38 / -44. | | | | THE DOOR PROPOSED DOES NOT MEET THE DESIGN PRESSURES | | SPECIFIED IN THE DOCUMENT THAT I PROVIDED. YOU CAN | | PROVIDE ENGINEERING OR CALCULATIONS FOR THE EXACT DOOR | | SIZE PROPOSED, OR PROPOSE A DOOR WHICH MEETS THE DESIGN | | PRESSURES. | | | | FBC R 301 |
|