2021-12-04 12:51:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE PRODUCT APPROVAL IS NOT UPLOADED PROPERLY. THE
 SPEC SHEETS ARE NOT CLEAR AND ARE UPSIDE DOWN. FBC 107,
 WHEN UPLOADING PRODUCT APPROVALS ENSURE THAT THEY ARE
 UPLOADED IN THE CORRECT ORIENTATION TO FACILITATE PLAN
 REVIEW.
  
 2. A DOCUMENT HAS BEEN UPLOADED TO YOUR FILE WHICH
 GIVES PRESCRIPTIVE WIND DESIGN LOADS FOR PALM BEACH
 COUNTY. YOU ARE PROPOSING A GARAGE DOOR THAT IS 8' X
 7'. SEE THE WIND LOAD CHART; IT DOES NOT INCLUDE THE
 DOOR SIZE 8' X 7' SO YOU NEED TO USE THE NEXT SIZE
 WHICH IS 6' X 7'.
  
 THE DESIGN PRESSURE REQUIREMENTS FOR A 6' X 7' DOOR,
 EXPOSURE C, IS +39.8 / -50.6. THE DOOR PROPOSED HAS A
 DESIGN PRESSURE LIMITATION OF +38 / -44.
  
 THE DOOR PROPOSED DOES NOT MEET THE DESIGN PRESSURES
 SPECIFIED IN THE DOCUMENT THAT I PROVIDED. YOU CAN
 PROVIDE ENGINEERING OR CALCULATIONS FOR THE EXACT DOOR
 SIZE PROPOSED, OR PROPOSE A DOOR WHICH MEETS THE DESIGN
 PRESSURES.
  
 FBC R 301