2022-02-01 10:37:02 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 21101362 |
| 2/1/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET LS.1.1, ARCH. & PLUMB. SHEETS: THE PLANS DO |
| NOT SHOW THE LOCATIONS OF THE REQUIRED DRINKING |
| FOUNTAINS FOR THE MERCANTILE AND ASSEMBLY OCCUPANCIES |
| ON THE 1ST FLOOR. IF CLAIMING THE EXCEPTION FOR |
| SUBSTITUTION UNDER SEC. 410.4 FOR THE A-2 FUTURE |
| RESTAURANT, PLEASE PLACE A NOTE ON THE PLANS. THERE IS |
| NO EXCEPTION FOR THE MERCANTILE OCCUPANCIES. |
| |
| 2) A9.0.1 DETAIL B: PLEASE SHOW THE REQUIRED 36-INCH |
| SHOWER OPENING MEASUREMENTS- SEC. 608.2.3 FBC ACC. |
| |
| 3) A9.02 DETAILS 1, 8, 13, 16: SHOW THE MINIMUM 9-INCH |
| HIGH TOE CLEARANCE AT THE LAV SINKS- SEC. 306.2 FBC |
| ACC. |
| |
| 4) A9.0.3 DETAIL 14: SHOW THE DRINKING FOUNTAIN SPOUT |
| HEIGHTS- SECS 602.4 & 602.7 FBC ACC. |
| |
| 5) P1.0, P5.3, & P5.4: GREASE INTERCEPTOR CALCULATIONS |
| FOR HYDROSTATIC-TYPE INTERCEPTORS SHALL NOT USE THE |
| NUMBER OF SEATS AS THE BASIS FOR SIZING. SIZING BY |
| SEATS IS AN OUTDATED FORMULA THAT WAS PREVIOUSLY USED |
| FOR GRAVITY TYPE INTERCEPTORS. SIZING FOR THE SCHIER |
| INTERCEPTORS SHALL BE DETERMINED BY THE EXPECTED |
| MAXIMUM FLOW IN GALLONS PER MINUTE THAT THE INTERCEPTOR |
| WILL RECEIVE- SEC. 1003.3.5 FBC P. PLEASE REVISE THE |
| CALCULATIONS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |