Plan Review Notes
Plan Review Notes For Permit 21101362
Permit Number 21101362
Review Stop P-GREASE
Sequence Number 1
Notes
Date Text
2022-02-01 10:38:502ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21101362
 2/1/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 5) P1.0, P5.3, & P5.4: GREASE INTERCEPTOR CALCULATIONS
 FOR HYDROSTATIC-TYPE INTERCEPTORS SHALL NOT USE THE
 NUMBER OF SEATS AS THE BASIS FOR SIZING. SIZING BY
 SEATS IS AN OUTDATED FORMULA THAT WAS PREVIOUSLY USED
 FOR GRAVITY TYPE INTERCEPTORS. SIZING FOR THE SCHIER
 INTERCEPTORS SHALL BE DETERMINED BY THE EXPECTED
 MAXIMUM FLOW IN GALLONS PER MINUTE THAT THE INTERCEPTOR
 WILL RECEIVE- SEC. 1003.3.5 FBC P. PLEASE REVISE THE
 CALCULATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  