Plan Review Notes For Permit 21101362 |
Permit Number |
21101362 |
|
Review Stop |
P-GREASE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-01 10:38:50 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 21101362 | | 2/1/2022 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 5) P1.0, P5.3, & P5.4: GREASE INTERCEPTOR CALCULATIONS | | FOR HYDROSTATIC-TYPE INTERCEPTORS SHALL NOT USE THE | | NUMBER OF SEATS AS THE BASIS FOR SIZING. SIZING BY | | SEATS IS AN OUTDATED FORMULA THAT WAS PREVIOUSLY USED | | FOR GRAVITY TYPE INTERCEPTORS. SIZING FOR THE SCHIER | | INTERCEPTORS SHALL BE DETERMINED BY THE EXPECTED | | MAXIMUM FLOW IN GALLONS PER MINUTE THAT THE INTERCEPTOR | | WILL RECEIVE- SEC. 1003.3.5 FBC P. PLEASE REVISE THE | | CALCULATIONS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|