2021-12-06 18:10:09 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21101362 |
| 12/6/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET AD2.1.1: PLEASE SUBMIT THE INTERIOR PLUMBING |
| DEMOLITION PLANS FOR THE PROJECT- SECTION 107.2.1 WPB. |
| THE NOTE ON THE PLAN INDICATES UNDER SEPARATE PERMIT |
| HOWEVER A PLUMBING REVIEW WAS NOT PERFORMED UNDER |
| PERMIT- 21080441. |
| |
| 2) AD2.1.1- PLUMBING DEMO NOTE 1: |
| A) UTILITY RELEASE - CITY OF WEST PALM BEACH WATER |
| DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM |
| "DEMOLITION APPLICATION" PLEASE *FAX THE COMPLETED |
| "DEMOLITION APPLICATION" FORM TO 561-822-2183. |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| B) IF A WATER TRUCK IS DESIRED FOR WATERING DOWN SITE, |
| DETAILS WILL BE REQUIRED. |
| IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, |
| THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM. |
| C) KEY NOTE DE27: PLEASE NOTE THAT A SEPARATE PERMIT IS |
| REQUIRED FOR REMOVAL OF THE BACKFLOW PREVENTER DEVICE |
| AT THE PROPERTY. REPLACEMENT OF THE BACKFLOW WILL ALSO |
| REQUIRE A SEPARATE PERMIT. PLEASE PLACE NOTES ON THE |
| PLAN FOR CLARIFICATION. FOR FURTHER INFORMATION ABOUT |
| THE BACKFLOW PREVENTER PLEASE CONTACT THE UTILITIES |
| DEPT. AT 561-822-2244. |
| |
| 3) LS.1.1: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR |
| RETAIL SPACES 112 & 113 (M), AND THE FUTURE KITCHEN AND |
| RESTAURANT (A2)- SEE TABLE 403.1 FBC P. PLEASE OUTLINE |
| THE RESTAURANT AREA AND PROVIDE THE OCCUPANCY |
| CLASSIFICATION AND OCCUPANT LOAD. PLEASE SHOW THE |
| FIXTURE LOCATIONS ON THE PLANS FOR THESE TENANT SPACES. |
| |
| 4) LS.3.1: PLEASE LABEL THE FIXTURE REQUIREMENTS AS |
| THIRD FLOOR INSTEAD OF SECOND FLOOR- SECTION 107.2.1 |
| WPB. |
| |
| 5) A9.0.1: DETAIL A- FBC ACC MISSING DETAILS AND |
| CORRECTIONS. |
| A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| WATER CLOSETS- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| LAVATORIES- 606.2. |
| C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| D) THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| SPACES FOR THE LAVATORIES- 603.2.3. |
| |
| 6) A9.0.1 DETAILS 2 & 8: PLEASE SHOW THE LENGTHS OF THE |
| SIDE GRAB BARS AS DEPICTED IN FIGURE 604.5.1. |
| |
| 7) A9.0.1 DETAILS 1 & 5: PLEASE SHOW THE LENGTHS OF THE |
| REAR GRAB BARS AS DEPICTED IN FIGURE 604.5.2. |
| |
| 8) A9.0.1 DETAILS 1 & 5: PLEASE SHOW THE HEIGHTS OF THE |
| MIRRORS FROM THE FINISHED FLOORS TO THE REFLECTIVE |
| SURFACES- 603.3. |
| |
| 9) A9.0.1 DETAILS 1 & 5: PLEASE RELOCATE THE WATER |
| CLOSET FLUSH CONTROLS TO THE OPEN SIDES OF THE |
| FIXTURES- 604.6. |
| |
| 10) A9.0.1: SHOW THE KNEE AND TOE CLEARANCES FOR THE |
| LAVATORIES IN RR 116 & RR 117- 606.2. |
| |
| 11) A9.0.1 DETAIL B- FBC ACC MISSING DETAILS AND |
| CORRECTIONS. |
| A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| WATER CLOSETS- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| LAVATORIES- 606.2. |
| C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| |
| 12) A9.0.2 DETAIL A- FBC ACC MISSING DETAILS AND |
| CORRECTIONS. |
| A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| WATER CLOSETS- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| LAVATORIES- 606.2. |
| C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| D) THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| SPACES FOR THE LAVATORIES- 603.2.3. |
| |
| 12) A9.0.2- DETAILS 4 & 6: PLEASE SHOW THE LENGTHS OF |
| THE SIDE GRAB BARS AS SPECIFIED IN FIGURE 604.5.1- FBC |
| ACC. |
| |
| 13) A9.0.2- DETAILS 3 & 5: PLEASE SHOW THE LENGTHS OF |
| THE REAR GRAB BARS AS SPECIFIED IN FIGURE 604.5 FBC |
| ACC. |
| |
| 14) A9.0.2- DETAILS 1 & 5: PLEASE SHOW THE HEIGHTS OF |
| THE MIRRORS FROM THE FINISHED FLOORS TO THE REFLECTIVE |
| SURFACES- 603.3 FBC ACC. |
| |
| 15) A9.02- DETAILS 6, 10, 12: SHOW THE CENTERLINES OF |
| THE TOILET PAPER DISPENSERS MEASURED FROM THE FRONTS OF |
| THE WATER CLOSETS- SECTION AND FIGURE 604.7 FBC ACC. |
| |
| 16) A9.0.2- DETAILS 8, 13, & 16: SHOW THE KNEE AND TOE |
| CLEARANCES FOR THE LAVATORIES- 606.2 FBC ACC. |
| |
| 17) A9.02: PLEASE CLARIFY IF THE URINAL IS INTENDED TO |
| BE ACCESSIBLE AND PROVIDE COMPLIANCE DETAILS- CLEAR |
| FLOOR SPACE DIAGRAM AND DIMENSIONS, RIM HEIGHT- 605.2 & |
| 605.3 FBC ACC. |
| |
| 18) A9.02 DETAIL A: THE 4'-1" LENGTH OF THE WOMEN'S |
| STANDARD TOILET STALL IS NOT IN COMPLIANCE. MINIMUM 56" |
| LENGTH REQUIRED FOR WALL HUNG WATER CLOSET STALLS- |
| SECTION 405.3.1 FBC P. |
| |
| 19) A9.03 DETAIL 6- PLEASE SHOW THE LENGTHS OF THE SIDE |
| GRAB BARS A DEPICTED IN FIGURE 604.5.1- FBC ACC. |
| |
| 20) A9.03 DETAIL 6: SHOW THE CENTERLINE OF THE TOILET |
| PAPER DISPENSER MEASURED FROM THE FRONTS OF THE WATER |
| CLOSETS- SECTION AND FIGURE 604.7 FBC ACC. |
| |
| 21) A9.0.3- DETAILS 8, 9, & 11: SHOW THE KNEE AND TOE |
| CLEARANCES FOR THE LAVATORIES- 606.2 FBC ACC. |
| |
| 22) A10.2.1- DETAIL 1: SHOW THE DEPTH OF THE SINK |
| COUNTER- 308.1 FBC ACC. |
| |
| 23) A10.2.1- DETAIL 1: SHOW THE MAXIMUM 25 INCHES |
| MAXIMUM KNEE CLEARANCE- 306.3 FBC ACC. |
| |
| 24) A10.2.1 DETAIL 1: SHOW THE MINIMUM 11-INCH KNEE |
| CLEARANCE AT 9 INCHES ABOVE THE FINISHED FLOOR, AND 8 |
| INCHES DEEP MINIMUM AT 27 INCHES ABOVE THE FLOOR- 306.3 |
| FBC ACC. |
| |
| 25) P1.0: CIVIL DRAWINGS ARE REFERENCED IN THE KEY |
| NOTES HOWEVER THE DRAWINGS WERE NOT PROVIDED- SECTION |
| 107.2.1 WPB. |
| |
| 26) P1.0, P5.2, & P5.3: PLEASE IDENTIFY OR LABEL THE |
| GREASE INTERCEPTORS AND SOLIDS INTERCEPTORS ON P5.2 & |
| P5.3 TO CORRELATE WITH THE PLUMBING PLAN LABELS WHICH |
| ARE GL-1, GL-2, SL-1, SL-2- SECTION 107.2.1 WPB. |
| |
| 26) P1.0, P5.2 & P5.3: PLEASE PLACE A NOTE ON THE PLAN |
| TO INDICATE SEPARATE PERMITS ARE REQUIRED FOR THE |
| INTERCEPTORS- SECTIONS 105.1 & 107.2.1 WPB. |
| |
| 27) P1.0 & P.5.3: THE GREASE INTERCEPTOR CALCULATIONS |
| INDICATE EXISTING TENANT, HOWEVER THE PLAN SHOWS TWO |
| NEW TENANT SPACES. PLEASE PROVIDE CALCULATIONS FOR EACH |
| NEW TENANT SPACE. PLEASE NOTE THE SPACES ARE IDENTIFIED |
| AS RETAIL 112 & 113. |
| |
| 28) P1.0 & P.5.3: SHOW THE LOCATION OF THE SAMPLING |
| PORT FOR GL-2- SECTION 1003.3.5 FBC P. |
| |
| 29) P1.0 KEYNOTE 2: INDICATE THE MAXIMUM DEVELOPED |
| LENGTH IN FEET OF THE SYSTEM- TABLE E201.1 FBC P. |
| |
| 30) P1.0 KEYNOTE 19: PLEASE INDICATE THE DISCHARGE |
| LOCATION OF THE SUMP LINE- 712.3.5 FBC P. |
| |
| 31) P1.0 KEYNOTES 20, 21, & 22: PLEASE REFER TO COMMENT |
| #1. |
| |
| 32) P1.0: SHOW THE LOCATION OF KEYNOTE 38 ON THE PLAN- |
| SECTION 107.2.1 WPB. |
| |
| 33) P1.0 KEYNOTE 44: PLEASE PROVIDE SUPPORT AND HANGING |
| DETAILS FOR INSTALLATION OF THE DRAIN PANS- SECTION |
| 107.2.1 WPB. |
| |
| 34) P1.0 KEYNOTE 55: INDICATE HOW ACCESS WILL BE |
| PROVIDED FOR THE BACKWATER VALVE- SECTION 714.3 FBC P. |
| |
| 35) P1.0: PLEASE PROVIDE ENLARGED PIPING DRAWINGS FOR |
| THE NEW ACCESSIBLE RESTROOMS 116 & 117- SECTION 107.2.1 |
| WPB. |
| |
| 36) P2.0 KEYNOTE 22: PLEASE PROVIDE ADDITIONAL |
| INFORMATION FOR THE SUMP LINE IN THE MECH CHASE. IS THE |
| CHASE A FIRE-RATED SHAFT OR PLENUM ENCLOSURE? PLEASE |
| NOTE THAT PVC PIPE IS COMBUSTIBLE MATERIAL AND MAY BE |
| RESTRICTED FROM INSTALLATION IN THE CHASE- SECTION |
| 602.2.1 FBC M. |
| |
| 37) P4.1: ROOF DRAINAGE: |
| A) PLEASE PROVIDE KEYNOTES FOR THE NEW ROOF DRAINS |
| (RD-1)- SECTION 107.2.1 WPB. |
| B) SHOW THE GPM DRAINAGE FLOW AT EACH NEW AND EXISTING |
| DRAIN LOCATION. PLEASE INCLUDE THE EXISTING VERTICAL |
| LEADER PIPE SIZES- 1106.1 FBC P. |
| C) SHOW THE DRAINAGE SLOPES OF THE ROOF TO THE DRAIN |
| LOCATIONS- 1101.7, 1105.1 FBC P. |
| |
| 38) P7.1: INDICATE HOW TEMPERED WATER WILL BE DELIVERED |
| FROM THE LAVATORIES- SECTION 419.5 FBC P. |
| |
| 39) P7.2 PLEASE INDICATE THE SIZE AND SLOPE OF THE |
| EXISTING SANITARY WASTE PIPE AND THE TOTAL DFU?S OF THE |
| SYSTEM- TABLE 710.1(1) FBC P. |
| |
| 40) P7.2: PLEASE PROVIDE A TOTAL DFU CALCULATION THAT |
| INCLUDES THE FUTURE FIXTURES ON THE 3RD FLOOR- TABLE |
| 710.1(1) FBC P. |
| |
| 41) P5.2: PLEASE NOTE THAT THE WPB BUILDING DEPT. DOES |
| NOT ALLOW ALL THE USE OF BARRIER-TYPE TRAP SEALS IN |
| KITCHEN AREAS OR OTHER AREAS WHERE GREASE, OIL, DEBRIS |
| OR OTHER SUBSTANCES ARE COLLECTED AND WHICH MAY CAUSE |
| FAILURE OF THE DEVICE- SECTION 1002.4.1.3 FBC P. |
| |
| 42) P5.1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW WATER |
| HEATERS AND THERMAL EXPANSION TANKS AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS AND INSTALLATION MANUALS- |
| SECTION 502.1 FBC P. |
| |
| 43) P6.1 & P6.2: PLEASE NOTE THAT MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION MANUALS FOR ALL |
| PLUMBING FIXTURES, APPLIANCES, AND DEVICES SHALL BE |
| ONSITE AT TIME OF INSPECTION- SECTION 107.2.1 WPB. IF |
| SUBMITTALS ARE TO BE DEFERRED PLEASE PROVIDE A LIST OF |
| PRODUCTS ON THE PLAN- SECTION 107.3.4.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |