2021-11-23 15:30:121ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21101362
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE SERVED BY THE MECHANICAL SYSTEMS INSTALLED
 UNDER THIS PROJECT. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 2) PLEASE SHOW THE CONDENSATE PIPING, MATERIAL AND
 TERMINATION LOCATION. FBC M 307
  
 3) PLEASE EXPLAIN THE NEED FOR THE GV-1?S FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  