Plan Review Notes For Permit 21101362 |
Permit Number |
21101362 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-22 15:46:14 | ALTERATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW THE OCCUPANCY LOAD FOR ALL UNITS/AREAS | | (SOME ARE THERE SOME ARE MISSING) - FBC 1004.1 | | | | 2) DRAWING LS.3.1 SHOWS EGRESS PATH THROUGH THE WALLS - | | PLEASE CLARIFY - FBC 1006.2 | | | | 3) DRAWING A1.2.2 - PLEASE SHOW THE DOOR MANEUVERING | | SPACE NEEDED TO EXIT THE RESTROOM (18" BESIDE THE DOOR) | | FBC A 404.2.4 | | | | 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET GRAB | | BAR LOCATION DIMENSIONS FROM THE CENTER OF THE TOILET | | PER FBC A 604.5.2 | | | | 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR | | LOCATION DIMENSIONS FROM THE FINISHED FLOOR TO THE | | BOTTOM OF THE "REFLECTIVE SURFACE" PER FBC A 603.3 | | | | 6) ACCESSIBLE RESTROOMS - PLEASE SHOW THE SHOWER GRAB | | BAR SIZES AND LOCATION DIMENSIONS PER FBC 608.3 | | | | 7) PLEASE SHOW THAT THE DOORS THAT OPEN INTO THE | | CORRIDOR COMPLY WITH FBC 1005.7.1 DOORS. | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | THAN ONE-HALF. | | | | |
|