Plan Review Notes
Plan Review Notes For Permit 21101362
Permit Number 21101362
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-22 15:46:14ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE OCCUPANCY LOAD FOR ALL UNITS/AREAS
 (SOME ARE THERE SOME ARE MISSING) - FBC 1004.1
  
 2) DRAWING LS.3.1 SHOWS EGRESS PATH THROUGH THE WALLS -
 PLEASE CLARIFY - FBC 1006.2
  
 3) DRAWING A1.2.2 - PLEASE SHOW THE DOOR MANEUVERING
 SPACE NEEDED TO EXIT THE RESTROOM (18" BESIDE THE DOOR)
 FBC A 404.2.4
  
 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET GRAB
 BAR LOCATION DIMENSIONS FROM THE CENTER OF THE TOILET
 PER FBC A 604.5.2
  
 5) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR
 LOCATION DIMENSIONS FROM THE FINISHED FLOOR TO THE
 BOTTOM OF THE "REFLECTIVE SURFACE" PER FBC A 603.3
  
 6) ACCESSIBLE RESTROOMS - PLEASE SHOW THE SHOWER GRAB
 BAR SIZES AND LOCATION DIMENSIONS PER FBC 608.3
  
 7) PLEASE SHOW THAT THE DOORS THAT OPEN INTO THE
 CORRIDOR COMPLY WITH FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
  