Plan Review Notes
Plan Review Notes For Permit 21101323
Permit Number 21101323
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-08 15:07:351ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21101323
 11/8/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1 & A3: THE PLANS SHOW A NEW SINK IN
 CAFE147. PLEASE PROVIDE PLUMBING AND ACCESSIBILITY
 DRAWINGS AND DETAILS- SECTIONS 107.2.1 &107.3.5.1.3
 WPB.
  
 2) A1 & A3: DRINKING FOUNTAINS ARE REQUIRED FIXTURES IN
 B OCCUPANCIES- TABLE 403.1 FBC P. PLEASE SHOW THE
 LOCATION OF THE REQUIRED FOUNTAIN, OR PROVIDE NEW
 INSTALLATION PLUMBING AND ACCESSIBILITY DRAWINGS AND
 DETAILS- SECTION 810.1 FBC EX.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  