2022-07-22 16:31:01 | FAILED |
| |
| 1) UPDATED COMMENT: STAFF WILL ACCEPT YOUR WEIGHTED |
| AVERAGE METHODOLOGY; HOWEVER, THE COMMENTS MUST BE |
| ADDRESSED TO SATISFY STAFF THAT THE HOUSE DOES NOT |
| EXCEED THE MAXIMUM HEIGHT ALLOWANCE. |
| |
| A. SHEET A-202 WAS NOT INCLUDED (SHEET A-201 WAS |
| UPLOADED IN ITS PLACE), SO STAFF WAS UNABLE TO VERIFY |
| THE UPDATED AVERAGE GRADE CALCULATION TABLE AND THE |
| SHEET A-100 INFORMATION FOR THE EAST SIDE OF THE |
| BUILDING. |
| B. THANK YOU FOR PROVIDING ELEVATION TAGS ALONG THE |
| SOUTH ELEVATION DRAWING TO MIRROR THE TAGS ON SHEET |
| A-100. THE NORTH, EAST AND WEST ELEVATION DRAWINGS MUST |
| ALSO INCLUDE THESE TAGS SO THAT STAFF CAN VERIFY THE |
| MEASURE POINTS WITHOUT NEEDING TO SCALE THE PLAN. WHEN |
| SCALING THE PLAN, THE WEST GRADE ELEVATION AT THE WEST |
| GUEST 1 (LOWER) AND WEST LAUNDRY (HIGHER) DO NOT MATCH |
| THE TABLE OR SHEET A-100. |
| C. THE SOUTH ELEVATION DRAWING LISTS THE 1ST FLOOR SLAB |
| AT 9.00 NAVD. HOWEVER, THE GRADE TAGS (ALSO SHOWN ON |
| SHEET C-1) AND THE GRADE CROSS HATCH ARE SHOWN ABOVE |
| THIS 9-FOOT MARK. THE GRADE THAT THE SLAB SITS ON |
| CANNOT BE HIGHER THAN THE TOP OF THE SLAB (AS EVIDENCED |
| BY SHEET S-411). ADDITIONALLY, THE AVERAGE FINISHED |
| GRADE IS NOT MEASURED FROM THE TOP OF THE POOL DECK |
| PAVERS, WHICH ARE THE VALUES USED BASED ON SHEET C-1). |
| THE BUILDING HEIGHT IS MEASURED FROM THE AVERAGE |
| FINISHED GRADE. |
| D. PLEASE EXPLAIN WHY THE NORTH ENTRY (37.83 LINEAR |
| FEET AT 6.29 FEET ELEVATION) DOES NOT INCLUDE THE LOWER |
| HEIGHTS SHOWN ADJACENT TO THE NORTH ENTRY WALL ON THE |
| WEST LIB POWDER AND EAST ? GUEST BATH (5.97 FEET |
| ELEVATION) FOR APPROXIMATELY 19 OF THE 38 FEET. THIS |
| WILL BRING THE 6.29-FOOT MEASURE DOWN. |
| |
| 2) UPDATED COMMENT: THERE ARE TWO SEPARATE KITCHEN |
| AREAS SHOWN, WHICH IS NOT PERMITTED IN A SINGLE-FAMILY |
| HOUSE. **** ALL SHEETS NEED TO BE UPDATED TO REFLECT |
| THE REMOVAL OF THE OVEN IN THE BUTLER PANTRY, INCLUDING |
| THE PIPING PLANS, THE POWER PLANS, THE ELECTRIC |
| SCHEDULES, AND THE MECHANICAL PLANS. -- ZONING WILL NOT |
| PASS THIS PERMIT UNTIL ALL PLANS REMOVE THE 2ND OVEN OR |
| INCLUDE THE NOTE THAT THERE WILL BE NO OVEN IN THE |
| BUTLER KITCHEN. HOWEVER, THE ELECTRIC SCHEDULE AND THE |
| POWER PLAN MUST BE REVISED SHOW THE REMOVAL OF THE OVEN |
| CIRCUIT, 240 OUTLET AND OVEN. |
| |
| 3) THE NEWLY SUBMITTED SHEET L1.0 SITE PLAN DOES NOT |
| MATCH THE APPROVED LANDSCAPE PERMIT PLAN, NOR DOES IT |
| MATCH THE LAYOUT SHOW ON SHEETS A-100 ARCHITECTURAL |
| SITE PLAN, C-1 SITE PLAN THE ELEVATION PLANS, AND S-101 |
| FOUNDATION PLAN. ALL PLANS MUST SHOW THE SAME, |
| ACCURATE, CODE COMPLIANT CONDITIONS. NOTE: SHEET C-1 |
| WAS NOT UPDATED TO REFLECT LATEST CHANGES, SO STAFF IS |
| UNABLE TO VERIFY CODE COMPLIANCE. |
| |
| 4) THE NEW SHEET L1.0 SHOWS A BBQ AREA AND OUTDOOR |
| SHOWER ON SCREENING WALL AND EXTENDED DECK WITHIN THE |
| REQUIRED FIVE-FOOT SIDE SETBACK. PROVIDE DETAILS ON |
| EACH OF THESE ITEMS. |
| |
| A. IF THE PAVED DECK IS LESS THAN 18 INCHES ABOVE |
| GRADE, IT MAY NOT BE LOCATED CLOSER THAN TWO FEET FROM |
| THE PROPERTY LINE. THIS WAS A COMMENT MADE UPON THE |
| FIRST PLAN REVIEW FOR THIS LOCATION, WAS CORRECTED AND |
| NOW APPLIES AGAIN. |
| B. A FIXED BBQ GRILL IS AN ACCESSORY STRUCTURE AND MUST |
| CONFORM TO THE REQUIRED MINIMUM SETBACKS. |
| C. THE SHOWER SCREEN WALL MAY NOT EXCEED SIX FEET ABOVE |
| THE GRADE OF THE PROPERTY TO THE SOUTH. THE SURVEY AND |
| SHEET C-1 INDICATE THAT THE EXISTING GRADE AT THE |
| PROPERTY LINE IN THIS LOCATION IS 3.4 FEET, WITH THE |
| PROPOSED DECK ELEVATION AT JUST UNDER NINE FEET. THIS |
| PROHIBITS ANY ADDITIONAL WALL HEIGHT AT THIS LOCATION. |
| D. NONE OF THE PIPING PLANS INCLUDE THIS NEW LAYOUT. |
| |
| 5) PLEASE DESCRIBE WHAT THE STORAGE RACK THAT IS NOW |
| SHOWN ON THE SOUTH SIDE OF THE BUILDING WILL BE USED |
| FOR AND PROVIDE AN ELEVATION DRAWING. |
| |
| 6) SEPARATE PERMITS ARE REQUIRED FOR THE ITEMS LISTED |
| BELOW. PLEASE NOTE THAT STAFF HAS NOT FULLY REVIEWED |
| ANY OF THE ITEMS AS PART OF THIS PERMIT APPLICATION TO |
| VERIFY THAT THE INFORMATION SHOWN COMPLIES WITH CODE |
| BUT HAS NOTED SOME ITEMS AS LISTED. THIS PERMIT REVIEW |
| IS ONLY FOR THE HOUSE. |
| |
| A. IRRIGATION |
| B. POOL - THE POOL CONFIGURATION HAS BEEN CHANGED. FULL |
| COMPLIANCE REVIEW WILL BE WITH THE REQUIRED POOL |
| PERMIT. |
| C. GENERATOR |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |
| |
| |